58
CONDENSING WATER
In the heating season, the extract air humidity
condenses to water. In new buildings, condensation
runoff can form rapidly. Condensed water must be
able to freely leave the unit. At some time before
the heating season begins (e.g. during autumn
maintenance), check that the condensing water
outlets in the bottom pool are not clogged. To
check this, pour some water into the pool. Clean as
required. Water must at all times be kept out of the
electrical system.
MOUNTING THE CONDENSING WATER
OUTLET
1. Push the main body of the condensing water
outlet downward from above, through the hole
in the bottom plate of the ventilation unit.
2. Push the tension pin downward from below
towards the main body.
3. Place the valve ball inside the housing of the
condensing water outlet.
4. Attach the housing to the condensing water
outlet.
3
0
30
4
9
5
4
3
5
625
685
4
6
5
655
8
0
2
3
mi
n
.
3
0
1
3
3
mi
n
.
8
Ø 8
Ø 22
The length of the
adjusting screw is 37 mm
Thread bar M8x35
Shorter thread upward
INSTALLATION
VALLOX 145 MV BASE
The base is optional. Adjust the base with adjusting legs to level it.
Remove the (4) rubber plugs at the bottom of the unit. Place the
unit on top of the base so that the bars of the base fit in the holes
at the bottom of the unit.
70 mm
NOTE
The standard Silent Klick condensing water outlet
installation requires 70mm of free space below
the ventilation unit.
INST
ALLA
TION
Содержание 096 MV
Страница 2: ...2 MANUAL...
Страница 60: ...60 TECHNICAL SPECIFICATIONS CERTIFICATE OF CONFORMITY 096 MV 110 MV AND 145 MV...