25
© Vallox • We reserve the right to make changes without prior notice
VENTILATION PROFILES
USING THE UNIT
MODIFYING THE BOOST PROFILE SETTINGS
To edit the Boost profile settings, proceed as follows:
1. Open the main display of the
Boost
profile.
2. Press the
Profile information
button.
3. Press the
Edit
button.
4. The fan speed setup opens.
5. Use the
Plus
and
Minus
buttons to set the
Boost
profile fan
speed as a percentage of the maximum output ratio.
6. Press the
Right arrow
button.
7. The temperature setup opens.
8. Set the desired supply air temperature for the
Boost
profile
by using the
Plus
and
Minus
buttons. The recommended
temperature is +15°C or 2—3°C below the room
temperature. You can adjust the temperature in the range of
+10°C – +25°C.
9. Press the
Right arrow
button.
10. The setup for automatic fan speed control based on the
relative humidity opens.
11. Use the
Plus
and
Minus
buttons to select whether the
automatic fan speed control, based on the relative humidity,
is used or not.
12. Press the
Right arrow
button.
13. The setup for automatic fan speed control based on the
carbon dioxide level opens.
14. Use the
Plus
and
Minus
buttons to select whether the
automatic fan speed control, based on the carbon dioxide
level, is used or not.
15. Press the
Right arrow
button.
16. A display for setting the profile timer opens.
17. Use the
Plus
and
Minus
buttons to select whether the profile
timer function is used or not. The options are:
Ć
On
— When the timer is on, the
Boost
profile is used only
for the period specified in the timer.
Ć
Off
— When the timer is off, the
Boost
profile is used until
you (or the Week clock) change the profile.
18. Press the
Right arrow
button.
19. A display for setting the profile timer duration opens.
20. Set the profile timer duration by using the
Plus
and
Minus
buttons.
21. Press the
OK
button.