VENTILATION PROFILES
USING THE UNIT
MODIFYING THE AWAY PROFILE SETTINGS
1. Open the main display of the
Away
profile.
2. Press the
Profile information
button.
3. Press the
Edit
button.
4. The fan speed setup opens.
5. Use the
Plus
and
Minus
buttons to set the
Away
profile fan
speed as a percentage of the maximum output ratio.
6. Press the
Right arrow
button.
7. The temperature setup opens.
8. Set the desired supply air temperature for the
Away
profile by using the
Plus
and
Minus
buttons. You can
adjust the temperature in the range +10°C ... +25°C. The
recommended temperature is +15°C or 2—3°C below the
room temperature.
9. Press the
Right arrow
button.
10. The setup for automatic fan speed control based on the
relative humidity opens.
11. Use the
Plus
and
Minus
buttons to select whether the
automatic fan speed control, based on the relative humidity,
is used or not.
12. Press the
Right arrow
button.
13. The setup for automatic fan speed control based on the
carbon dioxide level opens.
14. Use the
Plus
and
Minus
buttons to select whether the
automatic fan speed control, based on the carbon dioxide
level, is used or not.
15. Press the
OK
button.