SFP: 1,0 / 0,28
SFP: 1,5 / 0,42
SFP: 2,0 / 0,56
46
46
Sound power level in the supply air duct
by octave band L
w
, dB
Sound power level in the extract air duct
by octave band L
w
, dB
Adjustment position
31%
42%
47%
54%
59%
66%
72%
100%
31%
42%
47%
54%
59%
66%
72%
100%
Air flow dm
3
/s (l/s)
25.7
39.3
44.9
51.0
57.5
67.6
76.6
88.9
27.8
43.1
46.7
58.8
61.9
70.8
78.4
88.8
Air flow m
3
/h
92.52
141.48
161.64
183.6
207
243.36
275.76
320.04
100.08
155.16
168.12
211.68
222.84
254.88
282.24
319.68
Medium
frequency
of the
octave
band Hz
63
60
65
68
69
72
74
75
77
58
62
65
68
72
74
73
76
125
55
63
66
69
71
72
74
78
45
52
56
58
62
64
65
68
250
49
57
60
64
66
68
70
73
32
38
41
45
48
51
53
56
500
49
51
53
56
59
61
63
67
36
45
43
46
48
51
53
56
1000
46
53
55
58
60
62
63
65
31
37
39
42
43
45
47
50
2000
37
46
50
54
57
60
62
65
19
25
28
31
33
36
38
41
4000
27
39
43
47
50
53
56
60
*
*
13
16
21
23
26
30
8000
*
26
32
37
42
46
49
55
*
*
*
*
*
*
*
20
L
W
,dB
L
WA
, dB(A)
62
68
71
73
76
77
79
82
58
62
65
68
72
74
74
77
50
56
59
62
65
67
69
72
37
44
46
48
51
53
55
58
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m
2
sound absorption)
ADJUSTMENT POSITION / AIR FLOWS (supply/extract)
Adjustment position
31%
42%
47%
54%
59%
66%
72%
100%
Air flow dm
3
/s (l/s)
29/32
45/50
51/59
60/67
67/75
77/84
84/90
98/105
Air flow m
3
/h
104.4/115.2
162/180
183.6/212.4
216/241.2
241.2/270
277.2/302.4
302.4/324
352.8/378
L
pA
, dB (A)
24
32
32
35
37
40
42
45
Volume flow rate
Volume flow rate
Po
w
er
(W
)
FAN INPUT POWER
Product codes
Vallox 110 MV R
Vallox 110 MV L
Vallox number
3446650
3446750
HVAC code
7912039
7912040
Additional heating
radiator
Power, 900W
Air volumes
Supply Air
Extract Air
107 l/s, 386 m
3
/h, 100 Pa
113 l/s, 407m
3
/h, 100 Pa
Fans
Supply Air
Extract Air
0.119kW, 0.9A EC
0.119kW, 0.9A EC
Electrical
connection
230V, 50Hz 9.6 A (power
plug)
Operating
efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
75% A+
84%
0,9 (50 l/s) A
Enclosure
protection class
IP 34
Filters
Supply Air
Extract Air
G4 and F7
G4
Post-heating radi-
ator
Power, 900 W
Heat recovery
bypass
Automatic
Preheating radiator
–
Weight
64 kg
extract air
supply air
SUPPLY / EXTRACT AIR VOLUMES
SOUND VALUES
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS 110 MV
Input power (total W)
Airflow specified in the ventilation plan
(extract l/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <2.0 (kW
m
3
/s)
P
res
su
re
los
s
in
d
u
cts
.
Tota
l p
res
su
re
(P
a
)
Recommended
operating range
Содержание 096 MV
Страница 2: ...2 MANUAL...
Страница 60: ...60 TECHNICAL SPECIFICATIONS CERTIFICATE OF CONFORMITY 096 MV 110 MV AND 145 MV...