44
FAN INPUT POWER
Product codes
Vallox 096 MV R
Vallox 096 MV L
Vallox number
3474450
3474550
HVAC code
7912030
7912031
Additional heating
radiator
–
Air volumes
Supply Air
Extract Air
92 l/s, 331m
3
/h, 100 Pa
95 l/s, 342m
3
/h, 100 Pa
Fans
Supply Air
Extract Air
0.119kW, 0.9A EC
0.119kW, 0.9A EC
Electrical
connection
230V, 50Hz 5.1A (power
plug)
Operating
efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
75% A+
81%
1.0 (38 l/s) B
Enclosure
protection class
IP 34
Filters
Supply Air
Extract Air
G4 and F7
G4
Post-heating radi-
ator
Power, 900 W
Heat recovery
bypass
Automatic
Preheating radiator
–
Weight
53 kg
Sound power level in the supply air duct
by octave band L
w
, dB
Sound power level in the extract air duct
by octave band L
w
, dB
Adjustment position
11%
28%
44%
55%
62%
76%
86%
100%
11%
28%
44%
55%
62%
76%
86%
100%
Air flow dm
3
/s (l/s)
10.6
25.2
38.1
46.6
53.8
65.6
72.9
76.0
12.0
27.6
36.7
44.2
50.5
61.0
70.4
76.4
Air flow m
3
/h
38.16
90.72
137.16
167.76
193.68
236.16
262.44
273.6
43.2
99.36
132.12
159.12
181.8
219.6
253.44
275.04
Medium
frequency
of the
octave
band Hz
63
39
52
61
62
64
71
69
68
26
30
40
44
47
53
54
57
125
36
45
51
56
58
62
65
66
24
34
40
46
49
53
57
57
250
41
51
57
60
62
65
67
68
22
33
39
42
45
49
53
54
500
38
50
54
57
60
63
65
66
28
39
44
47
49
53
55
56
1000
34
48
54
57
59
62
64
65
23
36
42
45
48
51
54
55
2000
24
43
50
55
57
61
64
65
13
24
31
35
37
41
43
44
4000
16
32
42
47
49
54
56
58
16
17
21
24
26
30
33
33
8000
21
21
27
34
38
44
48
49
21
21
21
21
21
22
23
24
L
W
,dB
L
WA
, dB(A)
45
57
64
66
69
73
74
74
33
43
49
52
55
59
62
63
39
52
58
61
64
67
69
70
28
39
45
48
51
54
57
57
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m
2
sound absorption)
ADJUSTMENT POSITION / AIR FLOWS (supply/extract)
Adjustment position
11%
28%
44%
55%
62%
76%
86%
100%
Air flow dm
3
/s (l/s)
14/15
31/30
48/44
60/54
68/62
82/74
92/83
98/89
Air flow m
3
/h
50.4/54
111.6/108
172.8/158.4
216/194.4
244.8/223.2
295.2/266.4
331.2/298.8
352.8/320.4
L
pA
, dB (A)
23
29
35
38
41
44
46
47
Volume flow rate
P
res
su
re
los
s
in
d
u
cts
.
Tota
l p
res
su
re
(P
a
)
Input power (total W)
Airflow specified in the ventilation plan
(extract l/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <2.0 (kW
m
3
/s)
SFP: 1,0 / 0,28
OV
SFP: 1,5 / 0,42
SFP: 2,0 / 0,56
extract air
supply air
Volume flow rate
Po
w
er
(W
)
SUPPLY / EXTRACT AIR VOLUMES
SOUND VALUES
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS 096 MV