SFP: 1,0 / 0,28
SFP: 1,5 / 0,42
SFP: 2,0 / 0,56
48
48
Sound power level in the supply air duct
by octave band L
w
, dB
Sound power level in the extract air duct
by octave band L
w
, dB
Adjustment position
31%
42%
47%
54%
59%
66%
72%
100%
31%
42%
47%
54%
59%
66%
72%
100%
Air flow dm
3
/s (l/s)
36.2
56.3
67.3
80.7
92.9
105
116
128
40.5
63.8
73.8
87.9
98.8
110
122
136
Air flow m
3
/h
130.32
202.68
242.28
290.52
334.44
378
417.6
460.8
145.8
229.68
265.68
316.44
355.68
396
439.2
489.6
Medium
frequency
of the
octave
band Hz
63
41
50
56
58
59
64
67
69
35
45
49
51
51
56
58
58
125
45
53
56
59
62
65
68
71
33
43
46
49
49
54
56
59
250
50
54
57
61
63
66
68
70
24
32
37
40
40
45
47
49
500
48
53
56
59
60
63
65
68
37
43
46
48
48
52
54
56
1000
45
54
57
60
62
64
66
67
30
36
39
42
42
46
48
50
2000
35
46
50
55
58
61
64
66
22
32
34
38
38
43
45
48
4000
26
41
46
51
54
58
60
63
16
20
22
25
25
31
33
36
8000
21
32
38
45
49
53
56
59
21
21
21
21
21
24
26
28
L
W
,dB
L
WA
, dB(A)
54
60
64
67
69
72
74
77
41
49
53
55
57
60
61
63
49
57
60
63
66
68
70
73
36
42
45
48
50
52
54
56
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m
2
sound absorption)
ADJUSTMENT POSITION / AIR FLOWS (supply/extract)
Adjustment position
31%
42%
47%
54%
59%
66%
72%
100%
Air flow dm
3
/s (l/s)
36/39
56/62
68/74
81/89
92/98
105/113
116/126
131/142
Air flow m
3
/h
129.6/140.4
201.6/223.2
244.8/266.4
291.6/320.4
331.2/352.8
378/406.8
417.6/453.6
471.6/511.2
L
pA
, dB (A)
27
34
37
40
42
45
47
50
Volume flow rate
Po
w
er
(W
)
FAN INPUT POWER
Product codes
Vallox 145 MV R
Vallox 145 MV L
Vallox number
3475650
3475750
HVAC code
7912049
7912050
Additional heating
radiator
Power, 1500 W
Air volumes
Supply Air
Extract Air
150 l/s, 540m
3
/h, 100 Pa
155 l/s, 558m
3
/h, 100 Pa
Fans
Supply Air
Extract Air
0.175 kW, 1.25A
0.175 kW, 1.25A
Electrical
connection
230V, 50Hz 11.9 A (power
plug)
Operating
efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
75% A+
84%
0,9 (70 l/s) A
Enclosure
protection class
IP 34
Filters
Supply Air
Extract Air
G4 and F7
G4
Post-heating radi-
ator
Power, 900 W
Heat recovery
bypass
Automatic
Preheating radiator
–
Weight
88.0 kg
Volume flow rate
P
res
su
re
los
s
in
d
u
cts
.
Tota
l p
res
su
re
(P
a
)
extract air
supply air
SUPPLY / EXTRACT AIR VOLUMES
SOUND VALUES
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS 145 MV
recommended
operating range
OV
Input power (total W)
Airflow specified in the ventilation plan
(extract l/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <2.0 (kW
m
3
/s)
Содержание 096 MV
Страница 2: ...2 MANUAL...
Страница 60: ...60 TECHNICAL SPECIFICATIONS CERTIFICATE OF CONFORMITY 096 MV 110 MV AND 145 MV...