Appendix F - Communication Protocols-Ethernet IP MM147 - D4 Hot Melt Unit
166
Data Value Byte 4 and 5
This is the data that the PLC sends to the Melter to update a given parameter. This value is limited to the range listed
in the Data Index table, and will return an
Outside Range fault
otherwise.
Pump1 speed%...Pump4 speed% Byte 6 - 13
With each message from the PLC to the Melter, the PLC can send the Pump Manual speed down, to change the
pump pressures dynamically.
Receive Packet (Melter) Frame
Bit Definitions for Status Bytes 0 and 1
These are the response bytes sent back from the Melter at every message.
Bit 0: Melter Ready for Operation – 1 = Ready, 0 = Not Ready
Bit 1: Ready Delay Enabled – 1 = Enabled, 0 = OFF
Bit 2: System is in Alarm State – 1 = Alarm, 0 = No Alarm
Bit 3:
System is in Fault State – 1 = Fault, 0 = No Fault
Bit 4: Melter is Shutdown – 1 = Shutdown, 0 = Not Shutdown
Bit 5: Melter in Warmup State – 1 = Warmup active, 0 = Warmup not active
Bit 6: Melter in Setback – 1 = Setback active, 0 = Setback not active
Bit 7: Pump 1 Active – 1 = On, 0 = OFF
Bit 8: Pump 2 Active – 1 = On, 0 = OFF
Bit 9: Pump 3 Active – 1 = On, 0 = OFF
Bit 10: Pump 4 Active – 1 = On, 0 = OFF
Bit 11: Not used
Bit 12: Not used
Bit 13: Not used
Bit 14: Communication Fault (See Error Codes Section)
Bit 15: Communication Fault (See Error Codes Section)
Byte0, 1 Byte2 Byte3 Byte4, 5
Status
Data Index
Ch+1 Data
Byte6, 7 Byte8, 9
Channel
Ch Read Data
Byte10, 11 Byte12, 13 Byte14, 15
Ch+2 Data
Ch+3 Data
Ch+4 Data
Ch+5 Data
Содержание D4
Страница 1: ...D4 Hot Melt Unit Manual Number MM147 Revision Date 6 2018 ...
Страница 4: ......
Страница 10: ...Table of Contents MM147 D4 Hot Melt Unit 10 Module Status LED 170 Link Activity LED 170 ...
Страница 20: ...Section 2 Safety and Use MM147 D4 Hot Melt Unit 20 ...
Страница 22: ...Section 3 Basic Features MM147 D4 Hot Melt Unit 22 ...
Страница 35: ...MM147 D4 Hot Melt Unit Section 5 Setup 35 Section 5 Setup Control Panel ...
Страница 42: ...Section 5 Setup MM147 D4 Hot Melt Unit 42 Set Language Continued Next Page ...
Страница 43: ...MM147 D4 Hot Melt Unit Section 5 Setup 43 Set Language Continued ...
Страница 44: ...Section 5 Setup MM147 D4 Hot Melt Unit 44 Set Temperature Units ...
Страница 46: ...Section 5 Setup MM147 D4 Hot Melt Unit 46 Tank Temperature Hose Valve Temperature Continued Next Page ...
Страница 47: ...MM147 D4 Hot Melt Unit Section 5 Setup 47 Hose Valve Temperature Continued ...
Страница 54: ...Section 5 Setup MM147 D4 Hot Melt Unit 54 Beacon Alarm Setup Continued ...
Страница 55: ...MM147 D4 Hot Melt Unit Section 5 Setup 55 Beacon 2 ...
Страница 70: ...Section 5 Setup MM147 D4 Hot Melt Unit 70 Sequential Start Valve ...
Страница 100: ...Section 6 Operation MM147 D4 Hot Melt Unit 100 ...
Страница 106: ...Section 7 Maintenance MM147 D4 Hot Melt Unit 106 ...
Страница 110: ...Section 9 Specifications MM147 D4 Hot Melt Unit 110 Dimensions ...
Страница 112: ...Section 10 Part Number List MM147 D4 Hot Melt Unit 112 D4 Unit ...
Страница 113: ...MM147 D4 Hot Melt Unit Section 10 Part Number List 113 D4 Unit Continued ...
Страница 120: ...Section 10 Part Number List MM147 D4 Hot Melt Unit 120 D4 Base Unit 776xx392 ...
Страница 142: ...Section 11 Warranty MM147 D4 Hot Melt Unit 142 ...
Страница 144: ...Section 12 Service MM147 D4 Hot Melt Unit 144 ...
Страница 146: ...Appendix A Password Levels MM147 D4 Hot Melt Unit 146 Setting Level 0 as Default Continued ...
Страница 148: ...Appendix B Power Requirements MM147 D4 Hot Melt Unit 148 ...
Страница 150: ...Appendix C Instruction Sheets for Option Kits MM147 D4 Hot Melt Unit 150 ...
Страница 208: ...5 Valco Melton IS0343 Anybus Installation Installation Continued ...
Страница 245: ...Appendix E Communication Protocols Modus MM147 D4 Hot Melt Unit 162 ...