Appendix
0020181589_04 auroCOMPACT Installation and maintenance instructions
51
No.
Work
Inspection
(annual)
Mainten-
ance
(at least
every
2 years)
16
Install the compact thermal module.
Caution: Replace the seals.
X
17
If the volume of water is insufficient or the outlet temperature is not reached, replace the second-
ary heat exchanger if necessary.
X
18
Open the gas isolator cock, reconnect the product to the power mains and switch the product on.
X
X
19
Open the service valves, fill up the unit/heating installation so that the pressure is 1,0-1,5 bar
(depending on the static height of the system) and start the purge programme.
X
20
Perform a test operation of the product and heating installation, including hot water generation,
and purge the system once more if necessary.
X
X
21
Check the type of gas.
X
22
Carry out a visual inspection to check the ignition and combustion.
X
X
23
Check the CO
₂
content (the air ratio) of the product again.
X
24
Ensure that there is no gas, flue gas, hot water, condensate or solar fluid leaking from the
product. If required, intercept the leakage.
X
X
25
Check the solar fluid level and top it up, if necessary.
X
26
Check the fill level in the glycol container and the pressure in the glycol circuit.
If the pressure is below 1 bar, manually actuate the air trap and correct the glycol fill level.
X
X
27
Record the inspection/maintenance work carried out.
X
X
D
Status codes
–
Overview
Applicability:
Germany
Status code
Meaning
Heating mode
S.00
Heating mode: No heat demand.
S.01
Heating mode: Fan start-up.
S.02
Heating mode: Pump start.
S.03
Heating mode: Ignition of the burner.
S.04
Heating mode: Burner on.
S.05
Heating mode: Pump/fan overrun.
S.06
Heating mode: Fan overrun
S.07
Heating mode: Pump overrun.
S.08
Heating mode: Remaining burner anti-cycling time.
S.09
Heating calibration routine/modulation cut-off time.
DHW mode
S.20
DHW demand.
S.21
DHW mode: Fan start-up.
S.22
DHW mode: Pump pre-run.
S.23
DHW mode: Ignition of the burner.
S.24
DHW mode: Burner on.
S.25
DHW mode: Pump/fan overrun.
S.26
DHW mode: Fan overrun
S.27
DHW mode: Pump overrun.
S.28
Hot water burner anti-cycling time.
S.29
Hot water calibration routine/modulation cut-off time.
Special cases
S.30
Room thermostat is blocking heating mode.
S.31
Summer mode activated or no heat requirement from the eBUS controller.
S.32
Waiting mode because of fan speed deviation.