Mechanical
and
Electrical
Installation
VDF650
User
Manual
-
38
-
■
Precautions
on
the
Wiring
1
)
Power
input
terminalsR
,
S
or
R
,
S
,
T
–
The
cable
connection
on the
input
side of the
AC
drive
has
no phase sequence
requirement
.
–
The specifcation
and
installation method of
external power cables must
comply
with
the
local
safety
regulations
and
related
IEC
standards
.
–
Use copper conductors of a proper size as power cables according to the
recommended
values
in
section
8
.
3
.
2
)
DC
bus
terminals
(+), (-)
–
Terminals
(+)
and
(-)
of DC bus have residual voltage after the AC drive is
switched off
.
After indicator CHARGE goes off
,
wait at least 10 minutes before
touching
the
equipment
Otherwise
,
you
may
get
electric
shock
.
–
connecting
external
braking components
for
the AC
drive
of
22 kW
and
above
(
220 V
)
and 37
kW and
above
(
other
voltage
classes
),
do
not reverse
poles
(+)
and
(-).
Otherwise
,
it
may
damage
the
AC
drive
and
even
cause
a
fre
.
–
The
cable
length
of
the
braking
unit
shall
be
no
longer
than
10
m
.
Use
twisted
pair
wire
or
pair
wires
for
parallel
connection
.
–
Do not connect the braking resistor directly to the DC bus
.
Otherwise
,
it may
damage
the
AC
drive
and
even
cause
fre
.
3
)
Braking
resistor
connecting
terminals
(+),
PB
–
The connecting terminals of the braking resistor are effective only for the AC
confgured
with
the
built
-
in
braking
unit
.
–
The
cable
length
of
the
braking
resistor
shall
be
less
than
5
m
.
Otherwise
,
it
may
damage
the
AC
drive
.
4
)
External
reactor
connecting
terminals
P
, (+)
For the AC
drive of 37 kW and above
(
220 V
)
and 75
kW and above
(
other voltage
classes
),
remove the jumper bar across terminals P and
(+)
and install the reactor
between
the
two
terminals
.
5
)
AC
drive
output
terminals
U
,
V
,
W
–
The specifcation
and
installation method of
external power cables must
comply
with
the
local
safety
regulations
and
related
IEC
standards
.
–
Use copper conductors of a proper size as power cables according to the
recommended
values
in
section
8
.
3
.
–
The capacitor or surge absorber cannot
be connected to the
output side of the
AC
drive
.
Otherwise
,
it
may
cause
frequent
AC
drive
fault
or
even
damage
the
AC
drive
.
–
If the motor cable is too long
,
electrical resonance will be generated due to
the impact of distributed capacitance
.
This will damage the motor insulation
or generate higher leakage current
,
causing the AC drive to trip in overcurrent
protection
.
If the motor cable is greater than 100 m long
,
an AC output reactor
must
be
installed
close
to
the
AC
drive
.
6
)
Terminal
PE
–
This terminal
must
be
reliably
connected
to
the main earthing
conductor
.
Otherwise
,
it
may
cause
electric
shock
,
mal
-
function
or
even
damage
to
the
AC
drive.
Содержание VDF650 Series
Страница 1: ...VDF650 Series High Performance AC Drive...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions VDF650 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information VDF650 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions VDF650 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...