Function
Code
Parameter
Name
Setting
Range
Default
A6
-
20
Jump
point
of
AI3
input
corresponding
setting
-
100
.
0
%–
100
.
0
%
0
.
0
%
A6
-
21
Jump
amplitude
of
AI3
input
corresponding
setting
0
.
0
%–
100
.
0
%
0
.
5
%
The AI terminals
(
AI1 to AI3
)
of the VDF650 all support the corresponding setting jump
function
,
which fixes the AI input corresponding setting at the jump point when AI input
corresponding
setting
jumps
around
the
jump
range
.
For example
,
AI1 input voltage jumps
around
5
.
00 V and the jump
range is 4
.
90
–
5
.
10
V
.
AI1
minimum
input
0
.
00
V
corresponds
to
0
.
0
%
and
maximum
input
10
.
00
V
corresponds
to
100
.
0
%.
The
detected
AI1
input
corresponding
setting
varies
between
49
.
0
%
and
51
.
0
%.
If
you
set
A6
-
16 to 50
.
0
%
and A6
-
17 to
1
.
0
%,
then
the
obtained AI1 input
corresponding
setting
is
fxed
to
50
.
0
%,
eliminating
the
fuctuation
effect
.
Group
A7
:
User
Programmable
Function
Group
A8
:
Point
-
point
Communication
Function
Code
Parameter
Name
Setting
Range
Default
A8
-
00
Point
-
point
communication
selection
0
:
Disabled
1
:
Enabled
0
It
is
used
to
decide
whether
to
enable
point
-
point
communication
.
Point
-
point communication indicates direct communication between two or more VDF650
AC
drives
by
using
CANlink
.
The
master
gives
target
frequency
or
target
torque
to
one
or
multiple
slaves
according
to
its
own
frequency
or
torque
signal
.
If multiple AC drives are connected by using CANlink cards
,
the terminal resistor of the
CANlink
card
connected
to
the
end
AC
drive
shall
be
switched
on
.
If point
-
point
communication
is
enabled
,
the
CANlink
communication
addresses
of the
AC
drives
are
automatically
matched
without
special
setting
.
The
point
-
point
communication
rate
is
set
in
FD
-
00
.
Function
Code
Name
Setting
Range
Default
A8
-
01
Master
and
slave
selection
0
:
Master
1
:
Slave
0
This
parameter
is
used
to
determine
whether
the
AC
drive
is
master
or
slave
.
At
point
-
point
communication
,
you
only
need
to
set
the
CANlink
communication
baud
rate
.
The
communication
addresses
are
allocated
automatically
based
on
whether
the
AC
drive
is
master
or
slave
.
Содержание VDF650 Series
Страница 1: ...VDF650 Series High Performance AC Drive...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions VDF650 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information VDF650 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions VDF650 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...