Description
of
Function
Codes
VDF650
User
Manual
-
174
-
Value
Function
Description
19
Undervoltage
state
output
If
the
AC
drive
is
in
undervoltage
state
,
the
terminal
becomes
ON
.
20
Communication
setting
Refer
to
the
communication
protocol
.
21
Reserved
Reserved
.
22
Reserved
Reserved
.
23
Zero
-
speed
running
2
(
having
output
at
stop
)
If
the
output
frequency
of
the
AC
drive
is
0
,
the
terminal
becomes
ON
.
In
the
state
of
stop
,
the
signal
is
still
ON
.
24
Accumulative
power
-
on
time
reached
If
the
AC
drive
accumulative
power
-
on
time
(
P7
-
13
)
exceeds
the
value
set
in
P8
-
16
,
the
terminal
becomes
ON
.
25
Frequency
level
detection
FDT2
output
Refer
to
the
descriptions
of
P8
-
28
and
P8
-
29
.
26
Frequency
1
reached
Refer
to
the
descriptions
of
P8
-
30
and
P8
-
31
.
27
Frequency
2
reached
Refer
to
the
descriptions
of
P8
-
32
and
P8
-
33
.
28
Current
1
reached
Refer
to
the
descriptions
of
P8
-
38
and
P8
-
39
.
29
Current
2
reached
Refer
to
the
descriptions
of
P8
-
40
and
P8
-
41
.
30
Timing
reached
If
the
timing
function
(
P8
-
42
)
is
valid
,
the
terminal
becomes
ON
after
the
current
running
time
of
the
AC
drive
reaches
the
set
time
.
31
AI1
input
limit
exceeded
If
AI1
input
is
larger
than
the
value
of
P8
-
46
(
AI1
input
voltage
upper
limit
)
or
lower
than
the
value
of
P8
-
45
(
AI1
input
voltage
lower
limit
),
the
terminal
becomes
ON
.
32
Load
becoming
0
If
the
load
becomes
0
,
the
terminal
becomes
ON
.
33
Reverse
running
If
the
AC
drive
is
in
the
reverse
running
state
,
the
terminal
becomes
ON
.
34
Zero
current
state
Refer
to
the
descriptions
of
P8
-
28
and
P8
-
29
.
35
Module
temperature
reached
If
the
heatsink
temperature
of
the
inverter
module
(
P7
-
07
)
reaches
the
set
module
temperature
threshold
(
P8
-
47
),
the
terminal
becomes
ON
.
36
Software
current
limit
exceeded
Refer
to
the
descriptions
of
P8
-
36
and
P8
-
37
.
37
Frequency
lower
limit
reached
(
having
output
at
stop
)
If
the
running
frequency
reaches
the
lower
limit
,
the
terminal
becomes
ON
.
In
the
stop
state
,
the
signal
is
still
ON
.
38
Alarm
output
If
a
fault
occurs
on
the
AC
drive
and
the
AC
drive
continues
to
run
,
the
terminal
outputs
the
alarm
signal
.
39
Motor
overheat
warning
If
the
motor
temperature
reaches
the
temperature
set
in
P9
-
58
(
Motor
overheat
warning
threshold
),
the
terminal
becomes
ON
.
You
can
view
the
motor
temperature
by
using
U0
-
34
.
40
Current
running
time
reached
If
the
current
running
time
of
AC
drive
exceeds
the
value
of
P8
-
53
,
the
terminal
becomes
ON
.
Содержание VDF650 Series
Страница 1: ...VDF650 Series High Performance AC Drive...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions VDF650 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information VDF650 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions VDF650 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...