apfiff09 marine
VACON®
•
47
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.31.3
Acknowledge Mode
ID1641
Bits indicate whether specific safety functions are acknowledged automatically
by advanced safety option board or require acknowledge from outside.
0 = automatic, 1 = manual
FALSE
TRUE
b0
B0 = Start up (STO active) [ACK-
STO-Boot]
b1
B1 = STO [ACK-STO]
b2
B2 = SS1 [ACK-SS1]
b3
B3 = SS2 [ACK-SS2]
b4
B4 = SQS [ACK-SQS]
b5
B5 = SLS [ACK-SLS]
b6
B6 = SSR [ACK-SSR]
b7
B7 = SMS [ACK-SMS]
b8
B8 = SSM [ACK-SSM]
b9
B9 = SAR [ACK-SAR]
b10
B10 = SDI [ACK-SDI]
b11
b12
b13
b14
b15
V1.31.4
Safety Encoder Speed
ID1642
Encoder speed in RPM reported by advanced safety option board.
V1.31.5
Ramp Selection
ID1643
B1,B0 = SLS ramp
B3,B2 = SSR ramp
00 = none, 01 = ramp 1, 10 = ramp 2.