apfiff09 marine
VACON®
•
259
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
7.14.4
Free DIN Delay
This function is used when certain DIN signal needs On or Off delay before actual command is
given. For example, Reading from DIN Status Word: DIN1 status giving it a 1.00 s delay and then
writing it by ID number to ID403 Start 1, thus giving 1 second delay to start on drive side.
P2.14.7.1 ID.Bit Free Digital input delay ID1832
“ID.Bit Free
DIN
”
Select digital input from DIN Status Word to be delayed.
P2.14.7.2 On Delay ID1833
“
On Delay
”
This defines ON delay for the input signal.
P2.14.7.3 Off Delay ID1834
“
Off Delay
”
This defines OFF delay for the input signal.
P2.14.7.4 Mono Time
ID1836
“
Mono Time
”
This timer makes a pulse that last defined time. Pulse will start after On Delay time.
P2.14.7.5 Control Out ID ID1835
“
Control Out ID
”
Select the signal ID to be controlled by input signal. If inversion or parameter value other than
zero and one is needed this can be connected to DIN ID Control function ID1570, ID1590 or
1578 where desired values can be set and connected to correct parameter.
7.14.5
ID.Bit ID Control
This function is used when it is necessary to control a signal or parameter through e.g. Status Bit.
Controlling the parameter is done with the ID of the controlled parameter and the true and false
values of this function.
P2.14.8.1 IDbit ID Control ID1634
“
IDbit ID Control
”
This parameter will be in the format of xxxx.yy where xxxx refers to the ID of the signal and yy
refers to individual bit.
P2.14.8.2 Controlled ID
ID1618
“
Controlled ID
”
Select parameter ID controlled by ID1634.
P2.14.8.3 False Value
ID1632
“
FALSE Value
”
Set here the controlled parameter value when the value of ID1634 is LOW for the parameter
selected by ID1618. The function does not recognize decimals. Give, therefore, e.g. 10.00 Hz
as '1000'.
P2.14.8.4 True Value
ID1633
“
TRUE Value
”
Set here the controlled parameter value when the value of ID1634 is HIGH for the parameter
selected by ID1618. The function does not recognize decimals. Give, therefore, e.g. 20.00 Hz
as '2000'.