5.2.1 Monitoring values 2
V1.24.1
Current A
ID 1113
Unfiltered motor current, recommended signal for VACON
®
NCDrive monitoring.
Drive Synch Operation Master drive
This value is the total current of the system divided by number of drives in the
system (SbLastID). SbLastId cannot be changed; it needs to be set according to
how many drives are linked with system bus.
Drive Synch Operation Follower drive
This value is current of drive own power unit.
V1.24.2
Torque
%
ID 1125
Unfiltered motor torque.
V1.24.3
DC Voltage
V
ID 44
Unfiltered DC link voltage.
V1.24.4
Application Status Word
ID 43
“Status Word 1”
Application Status Word combines different drive statuses to one data word.
Recommended signal for VACON
®
NCDrive monitoring.
Application Status Word 1 ID43
FALSE
TRUE
b0
Flux not ready
Flux ready (>90%)
b1
Not in Ready state
Ready
b2
Not Running
Running
b3
No Fault
Fault
b4
Direction Forward
Direction Reverse
b5
Emergency Stop Active
Emergency Stop NOT Active
b6
Run Disabled
Run Enable
b7
No Warning
Warning
b8
Power positive
Power negative or Gen torque or current
limit active
b9
Parameter Set 1 Active (or no set used) Parameter Set 2 active
b10
Brake Chopper Operating
b11
No DC Brake
DC Brake is active
b12
No Run Request
Run Request
b13
No Limit Controls Active
Limit control Active
b14
External Brake Control OFF
External Brake Control ON
b15
Not used
Not used
V1.24.5
Shaft Frequency Hz
ID1124
Shaft Frequency used by motor control.