P2.12.1.6 FaultWarnIndicat
ID1940
With this parameter its possible to select how warning and fault indication as handled to
digital outputs and to fieldbus
0
= Static
Static signal, as long as warning or fault is active. Warning will disappear after
10 second when warning situation has passed. Fault requires a reset always.
1st fault
1st warning
2nd fault
2nd warning
Reset
10
Seconds
1
= Toggle
If there is a warning or fault already active a new warning or fault will toggle
signal for one second.
1st fault
1st warning
2nd fault
2nd warning
Reset
10
Seconds
2
= Marine
If there is a warning or fault already active a new warning or fault will toggle
signal for one second. Warning status will not disappear automatically after 10
second, to make warning signal disappear a reset signal is needed.
1st fault
1st warning
2nd fault
2nd warning
Reset
10
Seconds
Reset