P2.6.2.12 Scaling of Generating power limit
ID1088
“GenPowerLimSclng”
The generator power limit is equal to the parameter Generator Power Limit if value 'Not
Used' is selected. If any of the inputs is selected, the generator power limit is scaled
between zero and parameter P2.6.2.2 Generator Power Lim.
0
= Parameter
1
= AI1
2
= AI2
3
= AI3
4
= AI4
5
= FieldBus Scaling ID46 (Monitoring Value)
P2.6.2.13 Undervoltage power limit DC level
ID1611
“UV Power C Levl”
This parameter defines the DC voltage level when the special power limit function is
activated. When DC voltage goes below this level the power level defined by under
voltage power limit will be activated.
P2.6.2.14 Undervoltage power limit
ID1612
“UV Power Lim.”
Defines the power limit that is used when DC voltage is below parameter Undervoltage
power limit DC level (P2.6.2.13). The function is deactivated when this parameter value
is zero.
Power Limit
DC Level
UV Level
UV P Lim