7.12.2
Temperature sensor protections
The temperature protection function is used to measure temperatures and issue warnings and/or
faults when the set limits are exceeded. The marine application supports two OPT-BH and OPT-B8
board simultaneously. One can be used for the motor winding and one for the motor bearings.
P2.12.2.1 Number of used inputs in board 1
ID739
“
Board1 Channels
”
Select used temperature sensor combination with this parameter. See also the VACON
®
I/O boards manual.
0
= Not used (ID Write, value of maximum temperature can be written from fieldbus)
1
= Sensor 1 in use
2
= Sensor 1 & 2 in use
3
= Sensor 1 & 2 & 3 in use
4
= Sensor 2 & 3 in use
5
= Sensor 3 in use
Note:
If the selected value is greater than the actual number of used sensor inputs, the
display will read 200ºC. If the input is short-circuited the displayed value is
–
30ºC.
P2.12.2.2 Board 1 Temperature response
ID740
“Board1 Response”
0
= No response
1
= Warning
2
= Fault, stop mode after fault according to Stop Function
3
= Fault, stop mode after fault always by coasting
P2.12.2.3 Board 1 warning limit ID741
“
Board1
Warn.Limit”
Set here the limit at which the PT100 warning will be activated.
When individual warning and fault limits are activated this is first board first channel (1A).
P2.12.2.5 Board 1 fault limit
ID742
“
Board1
Fault Lim.”
Set here the limit at which the PT100 fault (F56) will be activated.
When individual warning and fault limits are activated this is first board first channel (1A).
P2.12.2.5 Number of used inputs in board 2
ID743
“
Board2 Channels
”
If you have two temperature sensor boards installed in your AC drive you can choose
here the combination inputs in use in the second board. See also the VACON
®
I/O
boards manual.
0
= Not used (ID Write, value of maximum temperature can be written from fieldbus)
1
= Sensor 1 in use
2
= Sensor 1 & 2 in use
3
= Sensor 1 & 2 & 3 in use
4
= Sensor 2 & 3 in use
5
= Sensor 3 in use
P2.12.2.6 Board 2 Temperature response
ID766
“Board2 Response”
0
= No response
1
= Warning
2
= Fault, stop mode after fault according to Stop Function
3
= Fault, stop mode after fault always by coasting