apfiff09 marine
VACON®
•
115
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
7.2.2.1
Inching function
Inching function will start the drive to reference speed without additional start command regardless of
the control place. Inching function requires enabling from digital input before command is accepted.
Inching is also disabled if there is a start command active from the active control place.
P2.2.7.9
Inching reference 1
ID1239
“Inching Ref 1”
P2.2.7.10 Inching reference 2
ID1240
“Inching Ref 2”
These parameters define the reference for the inching function. The references are
bidirectional and the reverse command does not affect the direction of the inching
reference.
Other parameters for inching function
-
Digital input selection: Enable Inching
-
Digital input selection: Inching 1
-
Digital input selection: Inching 2
-
Parameter: Inching Ramp
P2.2.7.11 Speed step
ID1252
“Speed Step”
VACON
®
NCDrive parameter to help adjusting the speed controller (see VACON
®
NCDrive Tools: Step Response). With this tool you can give step to speed reference
after the ramp control.