7.5.3 Delayed Digital Output 1 & 2
P2.5.6.1
Digital output 1 signal selection
ID486
“Dig.Out 1 Signal”
P2.5.7.1
Digital output 2 signal selection
ID489
“Dig.Out 2 Signal”
Connect the delayed digital output signal to the digital output of your choice with this
parameter. For more information about the TTF programming method, see chapter 4.
P2.5.6.2
Digital output function
ID312
“DO1 Content”
P2.5.7.2
Digital output 2 function
ID490
“DO2 Content”
0 =
“
Not used
”
1 =
“Ready”
The AC drive is ready to operate.
Common reasons when
‘R
eady
’
signals are missing:
o
Run enable signal is low
o
DC Voltage is too low
o
DC Voltage is too high
2 =
“Run”
The AC drive is modulating.
3 =
“
Fault
“
A fault trip has occurred
4 = “FaultI
nvert
”
No active faults in the drive.
5 =
“OverheatWarn”
Drive temperature has exceeded normal operation conditions. Temperature limit may
vary depending on drive type and size.
6 =
“ExtFaul/Warm”
External fault or warning depending on parameter response to external fault
7 =
“RefFaul/Warn”
Fault or warning depending on parameter Response to the 4mA reference fault
- occurs if analogue reference is 4
—
20 mA and signal is <4mA
8 =
“Warning”
Always if a warning is on
9 =
“Reversed”
Drive output frequency is negative
10 = “JogS
peed
Sel”
The jogging, preset or inching speed has been activated with digital input.
11 =
“At speed”
Induction motor: speed is within nominal slip of the reference.
PMS motor: output frequency is within 1 Hz of the reference.
12 =
“MotorRegAct”
One of the limit regulators is active.
13 =
“FreqLim1Sup”
Output frequency limit 1 supervision
The output frequency goes outside the set supervision low limit/high limit.
14 =
“FreqLim2up”
Output frequency limit 2 supervision
The output frequency goes outside the set supervision low limit/high limit.
15 =
“TorqLimSprv”
Torque limit supervision
The motor torque goes beyond the set supervision low limit/high .
16 =
“RefLimSprv”
Reference limit supervision
Active reference goes beyond the set supervision low limit/high limit.