16 - CONTROL MODE FROM TERMINAL
BOARD
To control the gate through external devices you need have to
connect devices with normally open contact between terminals
S1-S4
,
S2-S4
or
S3-S4
and set for each the desired function via
the parameters
ING1
,
ING2
and
ING3
.
The functions available are:
•
Start
(
START
value to be set)
This function corresponds to a generic activation command and
controls the following operations:
- When the gate is closed, an opening cycle starts
- When the gate is opening depends on the setting of parameter
ST.AP
:
NO
: command not active
CHIU
: the gate closes immediately
PAUS
: the gate stops (if the automatic closing mode is on the
pause time counting starts)
- When the gate is open and the pause the counting is not
active, the closing starts
- When the gate is open and the pause time counting is active,
depends on the menu
ST.PA
:
NO
: command not active
CHIU
: closing starts
PAUS
: reset the pause time counting
- When the gate is closing depends on the menu
ST.CH
:
APRE
: the gate re-opens
STOP
: the gate will stop and the cycle is considered finished
- When the gate is stopped due to a stop command or the
detection of an obstacle, a command Start restarts the gate in
the same direction as it was before being stopped.
If the parameter
STOP
is set to
INVE
the gate again moves,
but in the opposite direction.
- When the gate began a partial opening cycle commands a
total opening
•
Partial start
(
ST.PE
value to be set)
This function corresponds to a partial opening command and
controls the following operations:
- When the gate is closed, a partial opening cycle starts; the gate
opens only for the percentage of travel set in the parameter
P.APP
- When the gate began a normal opening cycle this command
has no effect.
- Once the gate has started a partial opening cycle, it is
dependent on the menu
SP.PA
:
PAUS
: the gate stops and pauses
CHIU
: the gate immediately starts closing
NO
: the gate continues to open (the command is ignored)
•
Stop
(
STOP
value to be set)
This function corresponds to a stop command: it is the only
case in which the connected device must work with normally
closed contact; it can be used to stop the gate and hold it in a
locked position.
The operation of the STOP command depends on the value set for
the parameter STOP:
-
PROS
: the gate stops in its current position and as long as the
contact is open no command is effective.
Once the contact is closed again, any start command restarts
the gate that follows its previous direction.
-
INVE
: the gate stops in its current position and as long as the
contact is open no command is effective.
Once the contact is closed again, any start command restarts
the gate in the opposite direction.
-
APRE
: the gate stops any movement and opens completely. If
an active safety device prevents the opening, the gate does not
move until the device involved is deactivated, then it opens.
So the gate remains locked in the open position until the STOP
contact closes again.
-
CHIU
: the gate does not stop the movement immediately, but
when it stops it closes.
If a safety device causes its re-opening, the operation is carried
out, then again closing is commanded.
When the gate is closed, it remains locked in this position until
the STOP contact is closed again.
•
Always opens
(
APRE
value to be set)
Always controls the opening, regardless of the position of the
gate, if the gate is already open, it is ineffective.
NOTE
: This command is not available for the input
ING3
.
•
Always closes
(
CHIU
value to be set)
Always control the closing: if the gate is already closed it is
ineffective.
NOTE
: This command is not available for the input ING3.
•
Force dead man mode
(
PRES
value to be set)
This command is available only on the input ING3: when the
contact is closed the unit is operating in dead man mode.
17 - REMOTE CONTROL MODE
The HEAVY1 unit is fitted for the connection of an MR series
receiver. The receiver has 4 channels, which can be associated
with the buttons on the remote control and can have the
following functions:
• Channels 1 and 2 trigger the opening cycle according to the
setting of the parameter
RX
:
START
: channel 1 is equivalent to START command and
channel 2 to PARTIAL START command
APCH
: channel 1 is equivalent to the command OPEN and
channel 2 to the command CLOSE
• Channel 3 is equivalent to the STOP command