Hallett Instruction Manual
Released on 8-Aug-19
– GH2B
Page 14
UV Pure Technologies Inc. © 2019
Warning
–
Use metal piping such as copper or stainless steel at the
outlet
of the UV unit since water temperatures can reach 176°F (80°C) if the UV
unit operates without water flow or the ability to purge.
DO NOT USE PVC
.
These fittings, pipe insulation, and any piping compatible with the plumbing
should be on hand before you begin installation. See Figure 4.2 and make a
list of all necessary components including solder, paste and thread sealant.
Bypass piping and valves that isolate the unit are optional, (but
recommended) as is a drain valve for draining the unit.
Tools Needed
pipe cutter, torch and other typical plumbing tools for modifying
piping
Wrench for tightening hose connections
Phillips screwdriver
Slotted screwdriver
Location
Warning
- The unit must be positioned vertically on a solid wall
(the
performance of the system will be adversely affected if mounted
horizontally or is subjected to vibrations).
The installation of the unit
(see Figures 4.1 through 4.4) should be done in compliance with all
applicable federal, state/provincial, and local regulations. We recommend
that the unit be installed by a qualified service technician. Failure to install
the system properly may result in property damage (leaks/flooding) or
personal injury (electrical shock) and will void warranty.
In a potable water application, the UV Pure unit should be installed
downstream of (after) any pre-treatment devices such as filters, water
softeners etc and also any pressure tanks. However, it must be installed
before any branches
in the piping so that
all
the water is disinfected before
splitting and distributing throughout the home or facility. The unit
must be
before
any chlorine injection system or this will void warranty.
Time Required
Please note that full installation of the Hallett requires shutting off the main
water supply for a number of hours. If disinfection is necessary, all pipes must
be treated and flushed. Once the unit is plugged in, the new UV lamps may
take from a few moments to several hours to reach full power depending on
the type of lamps. Having a Dose Alarm is normal with a new system (or with
newly installed lamps) until the lamps have reached full power.
Summary of Installation:
Unpack and install Hallett on a wall
Prepare connections to inlet and outlet ports
Install purge valve discharge line to a suitable drain line
Install optional shutoff solenoid valve
Install optional bypass & drain plumbing
Содержание Crossfire Technology Hallett 1000NC
Страница 41: ...Hallett Instruction Manual Released on 8 Aug 19 GH2B Page 41 UV Pure Technologies Inc 2019 Figure 7 9A...
Страница 50: ...Hallett Instruction Manual Released on 8 Aug 19 GH2B Page 50 UV Pure Technologies Inc 2019...
Страница 51: ...Hallett Instruction Manual Released on 8 Aug 19 GH2B Page 51 UV Pure Technologies Inc 2019...
Страница 52: ...UV Pure Technologies Inc 455 Milner Ave Unit 1 Toronto Ontario M1B 2K4 www uvpure com...