43
Initial Installation
QUALIFIED INSTALLERS ONLY
ONLY use this venting
diagram if your appliance
has been converted to LP.
Restrictor Setting: Find
the point on the graph where
your vent configuration
will terminate. Remember
to consider elbows in the
HORIZONTAL plane account for
horizontal distance as stated
above. Use the corresponding
exhaust restrictor setting
indicated on the graph. See
the following section in this
manual for restrictor details.
Your climate and altitude may
alter what restrictor is required
for your particular application.
Figure 62: 5” x 8” LP Vent Graph
**Vertical vent height does not account for elbows
Does your vent configuration fall
outside the limits?
Use our power
vent kit (50-3883) for a much broader
venting range.
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
HORIZONT
AL RUN (ft)
VER
TIC
AL RISE (ft)
10
Setting #2
#3
INSTALLATION
PROHIBITED
Propane [LP]
11 12 13
14 15 16
17 18 19
20
Setting #1
9
8
7
6
5
4
3
2
1
36” S 8x11
to 5x8 reducer
minimum rise