CALCULATED SUPPLY SETPOINT
In this menu the calculated supply setpoint for the zone
can be overidden. This temperature is used as setpoint
for the supply temperature.
To override the calculated supply setpoint:
1. Select
Calculated supply setpoint
.
2. Press the navigation wheel to confirm selection.
3. Select
Manual
.
4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation
wheel again.
MELTING SUPPLY SETPOINT
In this menu the supply temperature setpoint for
meltaway in the zone is set.
This menu is only shown if
Zone Setup
is set to
Meltaway
for the zone.
To set the melting supply temperature setpoint:
1. Select
Supply Setpoint
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 35 ˚C
Setting range: 5.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
MIN. SUPPLY TEMP.
In this menu the minimum allowed supply temperature
for the zone can be set. The supply temperature is not
allowed to fall below this value.
This menu is only shown if
Zone Setup
is set to
Stand
Alone Control
or
Smatrix Base PRO
.
To set the minimum allowed supply temperature:
1. Select
Min. supply temp
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation
wheel again.
MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature
for the zone can be set. The supply temperature is not
allowed to rise above this value.
This menu is only shown if
Zone Setup
is set to
Stand
Alone Control
or
Smatrix Base PRO
.
To set the maximum allowed supply temperature:
1. Select
Max. supply temp
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 90.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation
wheel again.
HEATING CURVE MELTAWAY
In this menu a heating curve for the zone, while
meltaway status is
IDLE
, can be enabled.
This menu is only shown if
Zone Setup
is set to
Meltaway
for the zone.
To enable the heating curve:
1. Select
Heating Curve
.
2. Press the navigation wheel to confirm selection.
3. Select
Enable
.
4. Confirm the new setting by pressing the navigation
wheel again.
IDLE SUPPLY SETPOINT
In this menu a setpoint for the zone, while meltaway
status is IDLE, can be set. This temperature is used as
setpoint for the supply temperature.
To set the IDLE supply setpoint:
1. Select
IDLE supply setpoint
.
2. Press the navigation wheel to confirm selection.
3. Set the override value.
Default: 8.0 ˚C
Setting range: 1.0 – 15.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.