MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature
for the zone can be set. The supply temperature is not
allowed to rise above this value.
This menu is only shown if
Zone Setup
is set to
Stand
Alone Control
or
Smatrix Base PRO
for the zone.
To set the maximum allowed supply temperature:
1. Select
Max. supply temp
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 90.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation
wheel again.
DHW SUPPLY SETPOINT
In this menu the supply temperature setpoint for
domestic hot water production is set.
This menu is only shown if
Zone Setup
is set to
Domestic Hot Water
for the zone.
To set the supply temperature setpoint:
1. Select
Supply Setpoint
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60.0 ˚C
Setting range: 5.0 – 95.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
OVERHEATING ALARM LIMIT
In this menu the overheating alarm limit for domestic
hot water production is set. If the supply temperature
is higher than the set limit during the time set in
Overheating alarm delay
, the alarm is triggered.
This menu is only shown if
Zone Setup
is set to
Domestic Hot Water
for the zone.
To set the overheating alarm limit:
1. Select
Overheating alarm limit
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 68.0 ˚C
Setting range: 65.0 – 120.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
OVERHEATING ALARM DELAY
In this menu the overheating alarm delay for the
overheating alarm limit of the zone is set. If the supply
temperature is higher than
Overheating alarm limit
,
during the set delay, the alarm is triggered.
This menu is only shown if
Zone Setup
is set to
Domestic Hot Water
for the zone
To set the overheating alarm delay:
1. Select
Overheating alarm delay
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10 min
Setting range: 0 – 15 min, 1 min increments