![Uponor Smatrix Move PRO Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/uponor/smatrix-move-pro/smatrix-move-pro_installation-and-operation-manual_1060916065.webp)
EXERCISE HOUR
In this menu the hour of the day for pump exercise is
set.
This menu is only shown if
Pump Exercise
is set to
Pump Exercise
.
To select an hour of the day for pump exercise:
1. Select
Exercise Hour
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 8 h
Setting range: 0 – 23 h, 1 h increments
4. Confirm the setting by pressing the navigation
wheel again.
EXERCISE MIN
In this menu the minute of the hour for pump exercise
is set.
This menu is only shown if
Pump Exercise
is set to
Pump Exercise
.
To select a minute of the hour for pump exercise:
1. Select
Exercise Min
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0 min
Setting range: 0 – 59 min, 1 min increments
4. Confirm the setting by pressing the navigation
wheel again.
Mixing Valve
This menu enables access to mixing valve settings in the
zone.
MENU TREE
Mixing Valve
P-area
I-time
Actuator running time
P-AREA
In this menu the P-area for the mixing valve regulation
is set.
To set the P-area:
1. Select
P-area
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Stand Alone Control/Smatrix Base PRO:
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
Domestic Hot Water:
Default: 70 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation
wheel again.