![Uponor Smatrix Move PRO Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/uponor/smatrix-move-pro/smatrix-move-pro_installation-and-operation-manual_1060916071.webp)
Indoor Temp. Settings
This menu enables access to settings related to the
room temperature sensor in the zone.
This menu and its submenus are only shown if
Heating
Mode
is set to
O Indoor comp.
.
MENU TREE*
Indoor Temp. Settings
Indoor Setpoint
Calculated Indoor Setpoint
ECO-Comf. Status
Indoor Setpoint Influence
(Lower)
Indoor Setpoint Influence
(UPPER)
*
Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
INDOOR SETPOINT
In this menu the indoor temperature setpoint for the
zone is set.
This information is only shown if
Zone Setup
is set to
Stand Alone Control
for the zone.
To set the indoor temperature setpoint:
1. Select
Indoor Setpoint
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 21.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
CALCULATED INDOOR SETPOINT
This menu shows the calculated indoor setpoint for the
zone.
This information is only shown if
Zone Setup
is set to
Stand Alone Control
and if ECO-Comf mode is set to
ECO for the zone.
ECO-COMF STATUS
This menu shows if the zone is set in ECO mode.
This information is only shown if ECO-Comf mode is set
to ECO for the zone.
INDOOR SETPOINT INFLUENCE (LOWER)
In this menu the indoor setpoint influence (lower) is set.
If the measured indoor temperature is higher than the
indoor temperature setpoint, the supply temperature
sepoint will be lowered using this value.
This menu is used to to keep the measured room
temperature as close as possible to the indoor
temperature setpoint.
N OT E !
If the value is set too high it can lead to
the system being unstable and the room
temperature will start fluctuating.
To set the indoor setpoint influence (lower):
1. Select
Indoor Setpoint Influence (Lower)
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
INDOOR SETPOINT INFLUENCE (UPPER)
In this menu the indoor setpoint influence (upper)
is set. If the measured indoor temperature is lower
than the indoor temperature setpoint, the supply
temperature sepoint will be increased using this value.
This menu is used to to keep the measured room
temperature as close as possible to the indoor
temperature setpoint.
N OT E !
If the value is set too high it can lead to
the system being unstable and the room
temperature will start fluctuating.
To set the indoor setpoint influence (upper):
1. Select
Indoor Setpoint Influence (Upper)
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation