3.3  Uponor Smatrix Move PRO 

components

C

ontroller

The controller operates the valve actuators and 
circulation pumps, which in turn affect the supply water 
temperature to the zone.

The temperature in up to four zones can be regulated 
by the controller.

Uponor Smatrix Move PRO Controller X-159

Main characteristics:

•  Integrated display with menu system.

•  Control of supply temperature for up to four zones 

(up to four heating systems, up to two snow melting 
zones, and one domestic hot water zone).

•  Heating curve (Stand Alone Control and Smatrix 

Base PRO zones only).

•  Connection of maximum four actuators (one per 

zone).

•  Connection of maximum four circulation pumps 

(one per zone).

•  Pump exercise.

•  Lower supply temperature using customizable 

schedules (ECO mode).

•  Initial setup done via startup wizard.

•  BMS ready via Modbus and KNX interfaces.

•  Integration with Uponor Smatrix Base PRO via 

system bus.

Options:

•  Cabinet or wall mounted using a DIN rail (not 

supplied).

Components of the controller

The illustration below shows the controller and its 
components with the heating application package.

A

B

microSD

1

1

23456789

10

11

12

13

14

15

16

17

18

41

42

45

48

51

54

56

44

43

47

50

53

46

49

52

55

12345678

91

01

11

21

31

41

51

61

71

8

11

23

4

23

4

12VDC IN

15VDC

GND

GND

24VAC IN

Base

PR

O

Base

PR

O

L

N

230 

V ± 10

%

50/60 Hz

2

AB

-

21

22

23

24

25

27

28

29

30

71

72

73

74

75

76

77

78

79

80

NL

26

mi

cr

oS

D

4

SM

AT

RIX BASE 
PRO – BU

S

3

3/

4

L

N

L

N

L

N

23

4

L

N

1

T

125 mA

 ≤ 

1A

 ≤ 

1A

 ≤ 

6A

 ≤ 

6A

Base

PR

O

!

!

!

!

L

N

230 V ± 10%

50/60 Hz

1

2

A

B

-

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

41

42

45

48

51

54

56

44

43

47

50

53

46

49

52

55

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

21

22

23

24

25

27

28

29

30

71

72

73

74

75

76

77

78

79

80

N

L

26

microSD

1

1

2

3

4

4

SMATRIX BASE

PRO – BUS

3

3/4

2

3

4

L

N

L

N

L

N

2

3

4

L

N

1

T

125 mA

12VDC IN

15VD

C

GN
D

GN
D

24

VA

C IN

 ≤ 

1A

 ≤ 

1A

 ≤ 

6A

 ≤ 

6A

Base
PRO

Base
PRO

Base
PRO

!

!

!

!

microSD

1

1

2

2

3

3

4

4

T

125 mA

L

N

230 V ±10%
50/60 Hz

microSD

L

N

L

N

L

N

L

N

1 2 3 4 5 6 7 8 9 10 11 12 13 14

16

52 53 54 55 56

52

50

49

48

46

45

43

42

-

+

+

-

+

-

+

-

72

26

25

24

23

22

21

B

A

-

73

75 76

77 78

79 80

GND

15VDC

12VDC IN

GND
24VAC IN

PRO

PRO

PRO

PRO

PRO

PRO

PRO

PRO

06 | 2016

Item

Description

A

Uponor Smatrix Move PRO Controller X-159

B

Heating only application package (microSD card, 
application diagram, connection stickers)

The box also contains a heating/cooling application 
package which is explained in another installation 
and operation manual.

EN

CZ

DE

DK

EE

ES

FI

FR

HR

HU

IT

LT

LV

NL

NO

PL

PT

RO

RU

SE

SK

7

U P O N O R   S M AT R I X   M O V E   P R O   ·   I N S TA L L AT I O N   A N D   O P E R AT I O N   M A N UA L

Содержание Smatrix Move PRO

Страница 1: ...05 2017 Uponor Smatrix Move PRO HEATI N G APPLI CATI ON EN I N STALLATI ON AN D OPERATI ON M AN UAL ...

Страница 2: ...e controller to AC power 28 5 13 Alternate power inputs 28 5 14 Startup wizard 28 5 15 Pre heating concrete slab DIN 1264 4 34 6 Finishing installation 36 7 Operate the Uponor Smatrix Move PRO controller 37 7 1 Principle of operation 37 7 2 Controller layout 37 7 3 Navigating the menu system 37 7 4 Start up 37 7 5 Information button 38 7 6 Main menu 38 7 7 System Overview 39 7 8 Information 39 7 9...

Страница 3: ...or is not connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and does not show evidence of tampering mishandling insufficient maintenance improper storage neglect or accidental damage before installation and being put into operation While Uponor has made efforts to ensure that the manual is accurate Uponor does not guarantee or warran...

Страница 4: ...ystem uses 50 Hz 230 V AC power In case of emergency immediately disconnect the power Technical constraints Caution To avoid interference keep installation data cables away from power cables of more than 50 V 2 2 Correct disposal of this product Waste Electrical and Electronic Equipment NOTE Applicable in the European Union and other European countries with separate collection systems This marking...

Страница 5: ...eeping large areas clear of snow 3 1 System overview Uponor Smatrix Move PRO consists of a controller and a wide array of sensors Together they control the supply temperature in each zone by managing the connected valve actuators and circulation pumps The zones can be setup as follows Zone Setup alternatives 1 Stand Alone Control Smatrix Base PRO 2 Stand Alone Control Smatrix Base PRO Domestic Hot...

Страница 6: ...is calculated using an outdoor sensor a ground temperature sensor and a ground moisture sensor When to start or stop snow melting status Stop Idle or Meltaway is determined by using an outdoor temperature sensor and two Uponor Smatrix Move PRO Sensor Snow S 158 sensors One of S 158 sensors is used for measuring the ground temperature and the other one is used for measuring the ground moisture leve...

Страница 7: ...6 49 52 55 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 1 2 3 4 2 3 4 12VDC IN 15VDC GND GND 24VAC IN Base PRO Base PRO L N 230 V 10 50 60 Hz 2 A B 21 22 23 24 25 27 28 29 30 71 72 73 74 75 76 77 78 79 80 N L 26 microSD 4 SMATRIX BASE PRO BUS 3 3 4 L N L N L N 2 3 4 L N 1 T 125 mA 1A 1A 6A 6A Base PRO L N 230 V 10 50 60 Hz 1 2 A B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 41 42 45 48 51 54 56...

Страница 8: ...s designed to be embedded into outdoor surfaces to measure the ground temperature and moisture level The sensor is only used in zones setup as Meltaway To ensure the snow melting function two Uponor Smatrix Move PRO Sensor Snow S 158 and three supply return sensors must be installed Main characteristics Detects moisture Detects temperature Horizontal installation to ensure collection of draining m...

Страница 9: ...ntroller is shown in the diagram below The diagram shows the calculated supply temperature for each curve at different outdoor temperatures The controller uses the selected curve to operate the mixing valve which in turn adjusts the supply temperature to the system 80 70 60 50 40 30 20 10 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 2 4 6 8 10 12 14 16 18 20 0 0 2 0 4 0 6 0 7 0 8 1 1 2 1 5 2 ...

Страница 10: ...hedules exist in the system some zones may still operate without any scheduling These zones will operate in constant Comfort mode and is not affected by the programming of other zones System integration with Base PRO systems The system can be integrated with an Uponor Smatrix Base PRO system to enable individual room control in the zone The outdoor temperature sensor is connected to the Base PRO s...

Страница 11: ...lation Verify the contents of the package with the packing list See also section 3 3 Uponor Smatrix Move PRO components for identification of components Study the wiring diagram in the end of this manual or on the controller L N 230 24 0 V 50 Hz 2 21 22 23 24 25 27 28 29 30 71 72 73 74 75 76 77 78 79 80 N L 26 microSD T 125 mA To determine where to best place the Uponor Smatrix Move PRO components...

Страница 12: ... manual Stand Alone Control A B If the zone 1 through 4 is setup as Stand Alone Control basic control of the system is enabled The following components are required for heating operation in the zone regulate the zone temperature using a mixing valve Supply sensor S 152 Optional Room sensor S 155 The outdoor temperature sensor is not needed if the Move PRO controller is integrated with an Uponor Sm...

Страница 13: ... activated in the Integration menu in the Base PRO interface in the startup wizard on the Move PRO controller See section 5 Install Uponor Smatrix Move PRO controller for more information SYSTEM SETTINGS IN STARTUP WIZARD Enable Zone 1 2 3 or 4 Yes Zone setup Smatrix Base PRO Heating Mode Outdoor outdoor temperature sensor only Outdoor Indoor comp outdoor temperature sensor with optional room temp...

Страница 14: ...taway hot water production for snow melting keeping large areas clear of snow is enabled in the zone The following components are required for snow melting hot water production in the zone regulate the supply temperature using a mixing valve Required Supply sensor S 152 Return sensor S 152 Primary return sensor S 152 not shown in illustration Snow sensor S 158 used as ground temperature sensor Sno...

Страница 15: ... 73 74 75 76 77 78 79 80 N L microSD L N L N 2 3 L N 1 T 125 mA A B 21 22 23 24 25 27 28 29 30 26 SMATRIX BASE PRO BUS 3 1 2 230 V 10 50 60 Hz I IN 1A I IN 6A I IN 6A Base PRO 25 26 3 microSD 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 41 42 45 48 51 54 56 44 43 47 50 53 46 49 52 55 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 1 2 3 4 2 3 4 12VDC IN 15VDC GND GND 24VAC IN Base PRO Base PRO L ...

Страница 16: ...71 72 73 74 75 76 77 78 79 80 N L 26 micro SD T 125 mA 5 7 Connect sensors to controller The following sensors can be connected to the system Uponor Smatrix Outdoor S 1XX Uponor Smatrix Move Sensor Supply Return S 152 Uponor Smatrix Move PRO Sensor Room S 155 Uponor Smatrix Move PRO Sensor Snow S 158 Warning Electrical installation and service behind secured 230 V AC covers must be carried out und...

Страница 17: ...he outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight 2 Ensure that the outdoor sensor is placed away from doors windows or air outlets N S E W Connect outdoor sensor to controller The illustration below shows the outdoor sensor connected to the controller 16 X 159 S 1XX To connect an outdoor sensor to the controller 1 Ensure that the power is di...

Страница 18: ...ing the wires to the connector Return sensor The return sensor only needs to be installed in zones setup as Meltaway or DHW domestic hot water Connect return sensor to controller The illustration below shows return sensors connected to the controller 4 6 11 X 159 S 152 3 2 4 To connect a return sensor to the controller 1 Study the wiring diagram to locate the connection terminal positions 2 Ensure...

Страница 19: ...not be heated through the wall by sunshine 4 Ensure that the room sensor is away from any source of heat for example television set electronic equipment fireplace spotlights and so on 5 Ensure that the room sensor is away from any source of humidity and water splashes IP20 1 3 1 5 m Label room sensor Label the room sensors where suitable with the zone numbers they are to control for example 02 03 ...

Страница 20: ...nnection terminal positions 2 Ensure that the power is disconnected from the controller 3 Remove the terminal cover See section 5 6 Terminal cover for more information 4 Route the wires through points A or B 5 Connect the wires from the room sensor to the controller ZONE 1 Terminals 2 and 2 ZONE 2 Terminals 4 and 4 ZONE 3 Terminals 6 and 6 ZONE 4 Terminals 11 and 11 6 Tighten the screws fixing the...

Страница 21: ...o allow draining melt water to collect on the sensor surface Not too deep though The snow sensor must be installed in an open unsheltered position away from walls and exposed to the elements eg not close to walls fan outlets or other sources which can affect the sensors If the snow sensor is to be used as a ground temperature sensor it must not be installed closer than 20 cm to the heating loop If...

Страница 22: ... where the sensor is to be installed Make sure it is securely embedded in relation to the expected surface load 3 Insert the supplied wood plug into the sensor tube before applying the concrete asphalt 4 Apply the concrete asphalt 5 Remove the wood plug when the concrete asphalt has cured 6 Ensure that the sunsor tube is clean 7 Insert the sensor cable and route it into the cable conduit Ensure th...

Страница 23: ...sensor to the controller 1 Study the wiring diagram to locate the connection terminal positions 2 Ensure that the power is disconnected from the controller 3 Remove the terminal cover See section 5 6 Terminal cover for more information 4 Connect the wires from the snow sensor to the controller ZONE 3 Pink wire to terminal 7 Grey wire to terminal 7 ZONE 4 Pink wire to terminal 12 Grey wire to termi...

Страница 24: ... may only need to be installed in zones setup as Meltaway Connect primary return sensor to controller The illustration below shows primary return sensors connected to the controller 9 14 X 159 S 152 3 4 To connect a primary return sensor to the controller 1 Study the wiring diagram to locate the connection terminal positions 2 Ensure that the power is disconnected from the controller 3 Remove the ...

Страница 25: ...e controller 1 Ensure that the power is disconnected from both the controller and the actuator 2 Remove the terminal cover See section 5 6 Terminal cover for more information 3 Study the wiring diagram to locate the connection terminal positions 4 Connect the wires from the actuator to the controller ZONE 1 0 10 V wire to terminal 43 Ground wire to terminal 42 ZONE 2 0 10 V wire to terminal 46 Gro...

Страница 26: ... power is disconnected from the controller 2 Remove the terminal cover See section 5 6 Terminal cover for more information 3 Study the wiring diagram to locate the connection terminal positions 4 Connect power max 230VAC to the circulation pumps external relays via connection terminals on the controller Caution The terminals are limited to 1A An external relay might be needed ZONE 1 Power L from t...

Страница 27: ...ntation for more information 4 Study the wiring diagrams of both controllers to locate the connection terminal positions 5 Connect the wires from the Base PRO controller to the Move PRO controller Uponor Smatrix Base PRO Communication wire to system bus terminal A B and Uponor Smatrix Move PRO Communication wire to system bus terminal 21 22 A and 23 B 6 Tighten the screws fixing the wires to the c...

Страница 28: ...cket or if required by local regulations to a junction box 5 13 Alternate power inputs The controller has connection terminals for alternate power inputs connection terminals 52 56 Caution Do not use these input terminals unless instructed to by Uponor technical support 5 14 Startup wizard The controller initiates a startup wizard the first time it is started or after a factory reset This wizard i...

Страница 29: ... system Language English Deutsch Espanol Swedish 2 Set the time Set the time of the system starting with the hours Time Enter the hours hh mm 12 34 Time Enter the minutes hh mm 12 34 3 Set the date Set the date of the system starting with the day Date Enter the day Tue 01 06 2016 Date Enter the month Tue 01 06 2016 Date Enter the year Tue 01 06 2016 EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL ...

Страница 30: ...O controller Stand Alone Control or to a connected Base PRO controller Smatrix Base PRO See section 5 7 Connect sensors to controller Outdoor sensor for more information Heating Mode Outdoor Outdoor Indoor comp 5 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a h...

Страница 31: ...etup menu Heating Mode Outdoor Outdoor Indoor comp 6 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a heating demand with the highest setpoint value in the zone Average calculates the average from all connected room thermostats in the zone selected in the Smatrix...

Страница 32: ...u Heating Mode Outdoor Outdoor Indoor comp 7 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a heating demand with the highest setpoint value in the zone Average calculates the average from all connected room thermostats in the zone selected in the Smatrix Base PR...

Страница 33: ...u Heating Mode Outdoor Outdoor Indoor comp 8 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a heating demand with the highest setpoint value in the zone Average calculates the average from all connected room thermostats in the zone selected in the Smatrix Base PR...

Страница 34: ...e heating is run in three different phases Pase 1 The supply temperature setpoint is set to 25 C for 3 days can be set in the Settings menu Pase 2 The supply temperature setpoint is set to maximum allowed calculated setpoint for 4 days can be set in the Settings menu Pase 3 The controller enters Standby mode until the startup wizard is restarted Settings Installer Settings Restart wizard Frost pro...

Страница 35: ...able to enable pre heating zone 2 in the controller Pre Heating Zone 2 Disable Enable 6 2 Set a maximum allowed calculated supply setpoint Z2 Max Calc Supply Setpoint min 5 0 max 70 0 45 0 C 7 Enable Pre Heating Zone 3 7 1 Select Enable to enable pre heating zone 3 in the controller Pre Heating Zone 3 Disable Enable 7 2 Set a maximum allowed calculated supply setpoint Z3 Max Calc Supply Setpoint m...

Страница 36: ...ach the terminal covers to the controller 3 Check the mixing valves Increase the setpoints in each zone to make sure the valves are opening correctly 4 Set system parameters in the controller to the defined operating settings 5 Print and fill in the Installation report located at the end of the manual 6 Give the manual and all information about the system to the user EN CZ DE DK EE ES FI FR HR HU ...

Страница 37: ...iption A Display B Navigation wheel OK button Used for navigating the menu system selecting options and confirming selections C Information button Used for showing current zone information such as supply temperature pump status etc Push the button repeatedly to switch zones D Back button 7 3 Navigating the menu system Select change Turn the control wheel to select an option or to change a paramete...

Страница 38: ...us Domestic Hot Water The following information is shown if the zone is setup as Domestic Hot Water Supply Temperature current supply temperature Pump status Mixing valve status Meltaway The following information is shown if the zone is setup as Meltaway Supply Temperature current supply temperature Outdoor Temperature current outdoor temperature Status current meltaway statu Stop Idle Melting Pro...

Страница 39: ...stem information menu shows the current time and date Zone 1 Information This menu shows information about zone 1 Menu tree Zone 1 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint Indoor temperature ECO Comf Status Mixing Valve Pump Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration Zone Setup ...

Страница 40: ...on is only shown if Zone Setup is set to Stand Alone Control Zone 2 Information This menu shows information about zone 2 Menu tree Zone 2 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint DHW Circ Return Temp Indoor temperature ECO Comf Status Mixing Valve Pump Parts of the menu tree may only be visible in the Move PRO controller depending on its curre...

Страница 41: ...g Valve The status of the mixing valve is shown 0 supply from heat source closed 100 supply from heat source fully opened Pump The status of the circulation pump is shown on off This information is only shown if Zone Setup is set to Stand Alone Control or Domestic Hot Water Zone 3 Information This menu shows information about zone 3 Menu tree Zone 3 Information Zone Setup Heating Mode Heating Curv...

Страница 42: ...or the zone This information is only shown if Zone Setup is set to Meltaway Return temperature The current return temperature is shown This information is only shown if Zone Setup is set to Meltaway Ground Temperature The current temperature in the ground around the snow sensor is shown This information is only shown if Zone Setup is set to Meltaway Ground Moisture This parameter shows if there is...

Страница 43: ...ntrol or Smatrix Base PRO Supply temperature The current supply temperature is shown The temperature is measured by the supply temperature sensor wired to the controller Calculated Supply Setpoint The calculated supply temperature is shown The setpoint is calculated using the sensor setup selected in Heating Mode Indoor temperature The current indoor temperature for the zone is shown If the zone i...

Страница 44: ...tion Protecting the heat source from low return temperatures The status may change in case of sensor fault An alarm will also be shown in the display if that is the case This information is only shown if Zone Setup is set to Meltaway Mixing Valve The status of the mixing valve is shown 0 supply from heat source closed 100 supply from heat source fully opened Pump The status of the circulation pump...

Страница 45: ...n wheel to confirm selection Alarm history This menu shows a list of the 10 latest alarms in the controller Each active alarm is presented with a short description about when it was logged and why it occured Detailed information is available via button press The detailed information shows alarm type time and date when it was logged the source of the alarm with severity PR1 to PR5 where PR5 is the ...

Страница 46: ...m selection 3 Set the value Default 0 C Setting range 50 50 C 1 C increments 4 Confirm the new setting by pressing the navigation wheel again Lock code A lock code can be used to block a user from changing parameter settings The menu system is fully accessible but the lock code is required to enter and change parameter settings The default lock code is 0000 It is recommended to change this code if...

Страница 47: ...Select Display contrast 4 Press the navigation wheel to confirm selection 5 Set the display contrast Setting range 50 100 1 increments 6 Press the navigation wheel to confirm selection Restore factory settings This menu enables all parameter settings in the controller to be reset to the factory default settings To restore the factory settings 1 Select Restore factory settings 2 Press the navigatio...

Страница 48: ...Zone 1 Settings Supply Temp Settings Indoor Temp Settings Comf ECO Heating Curve Manual Operation Pump Mixing Valve Seasonal Shut Off Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration Supply Temp Settings This menu enables access to settings related to the supply temperature in the zone MENU TREE Supply Temp Settings Calculated Supply Setp...

Страница 49: ...limit for the supply temperature in the zone is set If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay the alarm is triggered To set the deviation alarm limit 1 Select Deviation alarm limit 2 Press the navigation wheel to confirm selection 3 Set the value Default 10 0 C Setting range 0 0 50 0 C 0 ...

Страница 50: ... set If the measured indoor temperature is higher than the indoor temperature setpoint the supply temperature sepoint will be lowered using this value This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint NOTE If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating To set the ...

Страница 51: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Страница 52: ...wheel again HEATING CURVE This menu shows the heating curve and max min supply temperature limits for the zone Manual Operation This menu enables access to manual operation mode in the zone When manual operation mode is activated access to manual control override of the circulation pump and mixing valve is enabled MENU TREE Manual Operation Manual Mode Pump Mixing valve Parts of the menu tree may ...

Страница 53: ...the week for pump exercise is set This menu is only shown if Pump Exercise is set to Pump Exercise To select a day of the week for pump exercise 1 Select Exercise Day of the Week 2 Press the navigation wheel to confirm selection 3 Select a day Setting range Monday Sunday 4 Confirm the setting by pressing the navigation wheel again EXERCISE HOUR In this menu the hour of the day for pump exercise is...

Страница 54: ...the I time 1 Select I time 2 Press the navigation wheel to confirm selection 3 Set the value Default 35 seconds Setting range 5 300 seconds 1 second increments 4 Confirm the setting by pressing the navigation wheel again ACTUATOR RUNNING TIME In this menu the actuator running time for the mixing valve regulation is set To set the actuator running time 1 Select Actuator running time 2 Press the nav...

Страница 55: ... CLOSE In this menu a function to close the mixing valve when requirements are met is enabled To enable the function 1 Select Valve Close 2 Press the navigation wheel to confirm selection 3 Select Enable Default Disable Setting range Disable Enable 4 Confirm the setting by pressing the navigation wheel again SHUT OFF OUTDOOR TEMP In this menu the function to stop the circulation pump and or when t...

Страница 56: ... OFF INDOOR TEMP In this menu the function to stop the circulation pump and or when to close the mixing valve at an indoor temperature setpoint is enabled disabled for the zone This menu is only shown if Pump Stop and or Valve Close is enabled and if Heating Mode is set to Outdoor Indoor comp for the zone To set an shut off outdoor temperature 1 Select Shut Off Outdoor Temp 2 Press the navigation ...

Страница 57: ...ature is used as setpoint for the supply temperature This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone To override the calculated supply setpoint 1 Select Calculated supply setpoint 2 Press the navigation wheel to confirm selection 3 Select Manual 4 Set the override value Setting range 5 0 70 0 C 0 1 C increments 5 Confirm the new setting by press...

Страница 58: ...e overheating alarm limit for domestic hot water production is set If the supply temperature is higher than the set limit during the time set in Overheating alarm delay the alarm is triggered This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone To set the overheating alarm limit 1 Select Overheating alarm limit 2 Press the navigation wheel to confirm selection 3 Set the ...

Страница 59: ... Stand Alone Control Smatrix Base PRO Default 5 min Setting range 0 30 min 1 min increments Domestic Hot Water Default 60 seconds Setting range 0 600 seconds 1 second increments 4 Confirm the new setting by pressing the navigation wheel again Indoor Temp Settings This menu enables access to settings related to the room temperature sensor in the zone This menu and its submenus are only shown if Hea...

Страница 60: ...r Setpoint Influence Lower 2 Press the navigation wheel to confirm selection 3 Set the value Default 4 0 C Setting range 0 0 10 0 C 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again INDOOR SETPOINT INFLUENCE UPPER In this menu the indoor setpoint influence upper is set If the measured indoor temperature is lower than the indoor temperature setpoint the supply temper...

Страница 61: ...C 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again BOOSTPOWER In this menu the boost power for domestic hot water production is set The parameter is used to adjust the calculated supply temperature if the difference between the supply and return temperatures is to large This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone To set the boost...

Страница 62: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Страница 63: ...wheel again HEATING CURVE This menu shows the heating curve and max min supply temperature limits for the zone Manual Operation This menu enables access to manual operation mode in the zone When manual operation mode is activated access to manual control override of the circulation pump and mixing valve is enabled MENU TREE Manual Operation Manual Mode Pump Mixing valve Parts of the menu tree may ...

Страница 64: ...ller depending on its current configuration PUMP EXERCISE In this menu pump exercise can be activated To activate pump exercise 1 Select Pump Exercise 2 Press the navigation wheel to confirm selection 3 Select Pump Exercise Default No Exercise Setting range No Exercise Pump Exercise 4 Confirm the new setting by pressing the navigation wheel again EXERCISE DAY OF THE WEEK In this menu the day of th...

Страница 65: ...wheel to confirm selection 3 Set the value Default 0 min Setting range 0 59 min 1 min increments 4 Confirm the setting by pressing the navigation wheel again Mixing Valve This menu enables access to mixing valve settings in the zone MENU TREE Mixing Valve P area I time Actuator running time P AREA In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Pr...

Страница 66: ...conds 1 second increments 4 Confirm the setting by pressing the navigation wheel again Seasonal Shut Off This menu enables access to seasonal shut off settings in the zone This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO MENU TREE Seasonal Shut Off Pump Stop Valve Close Shut Off Outdoor Temp T Outdoor Setpoint T Outdoor Delay Shut Off Indoor Temp T Indoor Del...

Страница 67: ...utdoor temperature setpoint for stopping the circulation pump and or closing the mixing valve in the zone is set This menu is only shown if Shut Off Outdoor Temp is enabled To set an outdoor temperature setpoint 1 Select T Outdoor Setpoint 2 Press the navigation wheel to confirm selection 3 Select Enable Default 17 0 C Setting range 0 0 40 0 C 0 1 C increments 4 Confirm the setting by pressing the...

Страница 68: ...5 h 1 h increments 4 Confirm the setting by pressing the navigation wheel again Zone 3 Settings In this menu parameter settings for zone 3 can be set or changed Menu tree Zone 3 Settings Supply Temp Settings Indoor Temp Settings Comf ECO Heating Curve Meltaway Curve IDLE Status Return Temperature Enter Stop State Conditions Enter Idle State Conditions Enter Melting State Conditions Manual Operatio...

Страница 69: ... 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again MAX SUPPLY TEMP In this menu the maximum allowed supply temperature for the zone can be set The supply temperature is not allowed to rise above this value This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO To set the maximum allowed supply temperature 1 Select Max supply temp 2 P...

Страница 70: ...ng by pressing the navigation wheel again DEVIATION ALARM LIMIT In this menu the deviation alarm limit for the supply temperature in the zone is set If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay the alarm is triggered To set the deviation alarm limit 1 Select Deviation alarm limit 2 Press the...

Страница 71: ... the measured indoor temperature is higher than the indoor temperature setpoint the supply temperature sepoint will be lowered using this value This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint NOTE If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating To set the indoor ...

Страница 72: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Страница 73: ... menu enables access to meltaway heating curve settings for the zone while in IDLE status Settings such as the slope Setting and offset of the meltaway heating curve This menu is only shown if Zone Setup is set to Meltaway and if Heating Curve Meltaway is enabled for the zone MENU TREE Meltaway Curve IDLE Status Setting Offset Heating Curve SETTING In this menu the slope of the meltaway heating cu...

Страница 74: ...he value set in Outdoor Temperature for the number of days set in Delay days This menu is only shown if Zone Setup is set to Meltaway for the zone MENU TREE Enter Stop State Conditions Outdoor Temperature Delay days OUTDOOR TEMPERATURE In this menu the outdoor temperature used to switch meltaway state between IDLE and STOP is set To set the outdoor temperature 1 Select Outdoor Temperature 2 Press ...

Страница 75: ...ELTING to IDLE is set To set the outdoor temperature 1 Select Outdoor Temperature 2 Press the navigation wheel to confirm selection 3 Set the value Default 5 0 C Setting range 0 0 15 0 C 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again DELAY HOURS In this menu the number of delay hours used to switch meltaway state from STOP to IDLE is set To set the delay 1 Select...

Страница 76: ...lection 3 Select Low Limit 4 Press the navigation wheel to confirm selection 5 Set the value Default 2 C Setting range 0 10 C 1 C increments 6 Confirm the new setting by pressing the navigation wheel again OUTDOOR TEMP OFFSET In this menu the outdoor temperature offset used to switch meltaway state from IDLE to MELTING is set To set the outdoor temperature offset 1 Select Outdoor Temp Offset 2 Pre...

Страница 77: ...is menu the pump can be overidden and turned on or off manually To override the circulation pump operation 1 Select Pump 2 Press the navigation wheel to confirm selection 3 Select Manual 4 Select On Default Off Setting range Off On 5 Confirm the new setting by pressing the navigation wheel again MIXING VALVE In this menu the mixing valve can be overriden opened or closed manually To override the m...

Страница 78: ... of the Week 2 Press the navigation wheel to confirm selection 3 Select a day Setting range Monday Sunday 4 Confirm the setting by pressing the navigation wheel again EXERCISE HOUR In this menu the hour of the day for pump exercise is set This menu is only shown if Pump Exercise is set to Pump Exercise To select an hour of the day for pump exercise 1 Select Exercise Hour 2 Press the navigation whe...

Страница 79: ...the I time 1 Select I time 2 Press the navigation wheel to confirm selection 3 Set the value Default 50 seconds Setting range 5 300 seconds 1 second increments 4 Confirm the setting by pressing the navigation wheel again ACTUATOR RUNNING TIME In this menu the actuator running time for the mixing valve regulation is set To set the actuator running time 1 Select Actuator running time 2 Press the nav...

Страница 80: ...by pressing the navigation wheel again VALVE CLOSE In this menu a function to close the mixing valve when requirements are met is enabled To enable the function 1 Select Valve Close 2 Press the navigation wheel to confirm selection 3 Select Enable Default Disable Setting range Disable Enable 4 Confirm the setting by pressing the navigation wheel again SHUT OFF OUTDOOR TEMP In this menu the functio...

Страница 81: ... OFF INDOOR TEMP In this menu the function to stop the circulation pump and or when to close the mixing valve at an indoor temperature setpoint is enabled disabled for the zone This menu is only shown if Pump Stop and or Valve Close is enabled and if Heating Mode is set to Outdoor Indoor comp for the zone To set an shut off outdoor temperature 1 Select Shut Off Outdoor Temp 2 Press the navigation ...

Страница 82: ...ng by pressing the navigation wheel again Zone 4 Settings In this menu parameter settings for zone 3 can be set or changed Menu tree Zone 4 Settings Supply Temp Settings Indoor Temp Settings Comf ECO Heating Curve Meltaway Curve IDLE Status Return Temperature Enter Stop State Conditions Enter Idle State Conditions Enter Melting State Conditions Manual Operation Pump Mixing Valve Seasonal Shut Off ...

Страница 83: ... 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again MAX SUPPLY TEMP In this menu the maximum allowed supply temperature for the zone can be set The supply temperature is not allowed to rise above this value This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO To set the maximum allowed supply temperature 1 Select Max supply temp 2 P...

Страница 84: ...ng by pressing the navigation wheel again DEVIATION ALARM LIMIT In this menu the deviation alarm limit for the supply temperature in the zone is set If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay the alarm is triggered To set the deviation alarm limit 1 Select Deviation alarm limit 2 Press the...

Страница 85: ... the measured indoor temperature is higher than the indoor temperature setpoint the supply temperature sepoint will be lowered using this value This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint NOTE If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating To set the indoor ...

Страница 86: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Страница 87: ... menu enables access to meltaway heating curve settings for the zone while in IDLE status Settings such as the slope Setting and offset of the meltaway heating curve This menu is only shown if Zone Setup is set to Meltaway and if Heating Curve Meltaway is enabled for the zone MENU TREE Meltaway Curve IDLE Status Setting Offset Heating Curve SETTING In this menu the slope of the meltaway heating cu...

Страница 88: ...utdoor temperature is higher than the value set in Outdoor Temperature for the number of days set in Delay days MENU TREE Enter Stop State Conditions Outdoor Temperature Delay days OUTDOOR TEMPERATURE In this menu the outdoor temperature used to switch meltaway state between IDLE and STOP is set To set the outdoor temperature 1 Select Outdoor Temperature 2 Press the navigation wheel to confirm sel...

Страница 89: ...m STOP to IDLE state when the measured outdoor temperature is lower than the value set in Outdoor Temperature for the number of hours set in Delay hours The zone switches from MELTING to IDLE state when no moisture has been detected for the number of days set in Delay Surface Dry when the outdoor temperature is higher than the value set in Outdoor Temperature and when the ground temperature is hig...

Страница 90: ...ons Ground Temperature Limit Outdoor Temp Offset Outdoor Temperature Low Limit Min Time in Melting GROUND TEMPERATURE LIMIT In this menu the ground temperature limit used to switch meltaway state between IDLE to MELTING is set To set the ground temperature limit 1 Select Ground Temperature Limit 2 Press the navigation wheel to confirm selection 3 Select Low Limit 4 Press the navigation wheel to co...

Страница 91: ... This menu enables access to manual operation mode in the zone When manual operation mode is activated access to manual control override of the circulation pump and mixing valve is enabled MENU TREE Manual Operation Manual Mode Pump Mixing valve Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration To activate manual operation mode 1 Select Ma...

Страница 92: ...depending on its current configuration PUMP EXERCISE In this menu pump exercise can be activated To activate pump exercise 1 Select Pump Exercise 2 Press the navigation wheel to confirm selection 3 Select Pump Exercise Default No Exercise Setting range No Exercise Pump Exercise 4 Confirm the new setting by pressing the navigation wheel again EXERCISE DAY OF THE WEEK In this menu the day of the wee...

Страница 93: ...p exercise 1 Select Exercise Min 2 Press the navigation wheel to confirm selection 3 Set the value Default 0 min Setting range 0 59 min 1 min increments 4 Confirm the setting by pressing the navigation wheel again Mixing Valve This menu enables access to mixing valve settings in the zone MENU TREE Mixing Valve P area I time Actuator running time P AREA In this menu the P area for the mixing valve ...

Страница 94: ...access to seasonal shut off settings in the zone This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO MENU TREE Seasonal Shut Off Pump Stop Valve Close Shut Off Outdoor Temp T Outdoor Setpoint T Outdoor Delay Shut Off Indoor Temp T Indoor Delay Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration PUMP STOP I...

Страница 95: ...value Default 24 h Setting range 0 24 h 1 h increments 4 Confirm the setting by pressing the navigation wheel again VALVE CLOSE In this menu a function to close the mixing valve when requirements are met is enabled To enable the function 1 Select Valve Close 2 Press the navigation wheel to confirm selection 3 Select Enable Default Disable Setting range Disable Enable 4 Confirm the setting by press...

Страница 96: ... 1 h increments 4 Confirm the setting by pressing the navigation wheel again Automatic Freeze Protection This menu decides when to activate automatic freeze protection during meltaway in the zone The controller will kepp the return temperature between the low and high thersholds This menu is only shown if Zone Setup is set to Meltaway for the zone MENU TREE Automatic Freeze Protection Primary retu...

Страница 97: ... system is set To set the date 1 Select Date 2 Press the navigation wheel to confirm selection 3 Set the day 4 Press the navigation wheel to confirm selection 5 Set the month 6 Press the navigation wheel to confirm selection 7 Set the year 8 Confirm the setting by pressing the navigation wheel again Language In this menu the language of the system is set To set the language 1 Select Language 2 Pre...

Страница 98: ...ature The current supply temperature is shown The temperature is measured by the supply temperature sensor wired to the controller State The current pre heating state phase in the zone is shown Pre heating is run in three different phases Pase 1 The supply temperature setpoint is set to 25 C for 3 days can be set in the Settings menu Pase 2 The supply temperature setpoint is set to maximum allowed...

Страница 99: ...pre heating phase in the zone is shown Zone 3 Information This menu shows information about zone 3 Menu tree Zone 3 Information Supply temperature State Time Left Supply temperature The current supply temperature is shown The temperature is measured by the supply temperature sensor wired to the controller State The current pre heating state phase in the zone is shown Pre heating is run in three di...

Страница 100: ...t The time left of the current pre heating phase in the zone is shown Controller Information This menu shows information about the controller Menu tree Controller Information Language About Language This menu show the set display language for the controller About This menu shows the serial number software versions and hardware versions of the controller 7 12 Pre Heating Settings In this menu insta...

Страница 101: ...m selection 3 Enter the lock code in the boxes using the navigation wheel Turn the navigation wheel to either select a box or to increase decrease a value in edit mode Press the navigation wheel to enter edit mode or to confirm the new setting Default 0000 4 Confirm the lock code by pressing and holding the navigation wheel for a number of seconds 5 Change the parameter setting and exit Change loc...

Страница 102: ...backup 1 Make sure the microSD card with the backup is inserted into the controller 2 Select Restore backup 3 Press the navigation wheel to confirm selection 4 Select Yes Setting range No default Yes 5 Press the navigation wheel to confirm selection 6 All parameters in the controller are being restored from backup New backup This menu enables the controller to save a backup of all parameter settin...

Страница 103: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 140 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Страница 104: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 200 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Страница 105: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 200 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Страница 106: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 200 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Страница 107: ...the setting by pressing the navigation wheel again Language In this menu the language of the system is set To set the language 1 Select Language 2 Press the navigation wheel to confirm selection 3 Select a language 4 Confirm the setting by pressing the navigation wheel again Operation mode In this menu the operation mode of the system is set This setting is used to change from pre heating to stand...

Страница 108: ...ing Valve Pump Zone 2 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint DHW Circ Return Temp Indoor temperature ECO Comf Status Mixing Valve Pump Zone 3 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint Indoor temperature ECO Comf Status Meltaway Curve Return temperature Ground Temperature Ground Moisture P...

Страница 109: ...tings T Outdoor Fallback Lock code Change lock code Display settings Restore factory settings Restore backup New backup Restart wizard Zone 1 Settings Supply Temp Settings Calculated Supply Setpoint Min Supply Temp Max Supply Temp Deviation alarm limit Deviation alarm delay Indoor Temp Settings Indoor Setpoint Calculated Indoor Setpoint ECO Comf Status Indoor Setpoint Influence Lower Indoor Setpoi...

Страница 110: ...ed Supply Setpoint Min Supply Temp Max Supply Temp DHW Supply Setpoint Overheating alarm limit Overheating alarm delay Deviation alarm limit Deviation alarm delay Indoor Temp Settings Indoor Setpoint Calculated Indoor Setpoint ECO Comf Status Indoor Setpoint Influence Lower Indoor Setpoint Influence UPPER DHW Circ Return Settings DHW Circ Return Setpoint BoostPower Comf ECO ECO Setback ECO Comf St...

Страница 111: ...Melting Supply Setpoint Min Supply Temp Max Supply Temp Heating Curve Meltaway IDLE Supply Setpoint Min Supply Temp IDLE Status Max Supply Temp IDLE Status Deviation alarm limit Deviation alarm delay Indoor Temp Settings Indoor Setpoint Calculated Indoor Setpoint ECO Comf Status Indoor Setpoint Influence Lower Indoor Setpoint Influence UPPER Comf ECO ECO Setback ECO Comf Status ECO Comf Schedule H...

Страница 112: ... Low Limit Min Time in Melting Manual Operation Manual Mode Pump Mixing valve Pump Pump Exercise Exercise Day of the Week Exercise Hour Exercise Min Mixing Valve P area I time Actuator running time Seasonal Shut Off Pump Stop Valve Close Shut Off Outdoor Temp T Outdoor Setpoint T Outdoor Delay Shut Off Indoor Temp T Indoor Delay Automatic Freeze Protection Primary return Temp Low Primary return Te...

Страница 113: ...Schedule Heating Curve Setting Offset Heating Curve Meltaway Curve IDLE Status Setting Offset Heating Curve Return Temperature Max Supply Return Diff Enter Stop State Conditions Outdoor Temperature Delay days Enter Idle State Conditions Outdoor Temperature Delay hours Delay Surface Dry Enter Melting State Conditions Ground Temperature Limit Outdoor Temp Offset Outdoor Temperature Low Limit Min Tim...

Страница 114: ...Pre Heating Operating Mode System Overview Pre Heating Info System information Time Date Zone 1 Information Z1 Supply Temperature State Time Left Zone 2 Information Z2 Supply Temperature State Time Left Zone 3 Information Z3 Supply Temperature State Time Left Controller Information Language About Alarms Active alarms Alarm history Acknowledge all alarms Reset alarm history EN CZ DE DK EE ES FI FR ...

Страница 115: ...area I time Actuator running time Zone 2 Settings Z2 Max Calc Supply Setpoint Frost Protection Setpoint P area I time Actuator running time Zone 3 Settings Z3 Max Calc Supply Setpoint Frost Protection Setpoint P area I time Actuator running time Controller Settings Time Date Language Operation mode EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 115 UPONOR SMATRIX MOVE PRO INSTALLAT...

Страница 116: ...if enabled in the Move PRO controller display The pump is activated for 1 minutes during the exercise 8 3 Corrective maintenance Fallback mode If a sensor is malfunctioning or not detected the controller triggers an alarm and executes the fallback mode to maintain the temperature in the zone until the problem is resolved Resetting the controller If the controller does not work as expected for exam...

Страница 117: ...u system changes after the room sensor is moved The room sensor may be influenced by an external heat source Change location of the room sensor The indicator on the mixing valve actuator does not change move The mixing valve does not open 1 Check that the mixing valve is correctly installed 2 Contact the installer 3 Replace the mixing valve The room is too warm Corresponding loop is warm even afte...

Страница 118: ... installation report in the end of this document Prepare the following information before contacting an installer Installation report Drawings of the underfloor heating system if available List of all alarms including time and date 9 3 Installer instructions To determine if a problem is caused by the supply system or the control system loosen the actuators from the manifold for the room concerned ...

Страница 119: ... input 24 V AC 0 7A maximum 6 A Internal fuse 125 mA Sensor inputs Supply temperature sensor NTC 10 50 C 100 C 0 1 C Return temperature sensor Room temperature sensor Outdoor temperature sensor Ground temperature sensor Snow and ice sensor Moisture sensor Snow and ice sensor ROFF Ω RON 2MΩ Outputs Mixing valves UO 0 10V IO 10 mA Snow sensor UO 24 V AC PO 10 VA Circulation pumps UIN 230 V AC IIN 1 ...

Страница 120: ...5 mm flexible with ferrules 10 3 Controller layout F E J K I H G C D B L M N A Item Description A Display B Sensor input connection terminals C Mixing valve output connection terminals D Battery and transformer input connection terminals E microSD F BMS MODBUS RTU RS 232 connection G Uponor Smatrix Base PRO bus connection terminals H Snow and ice sensor output connection terminals I Circulation pu...

Страница 121: ... 3 4 5 6 7 8 9 10 11 12 13 14 16 52 53 54 55 56 51 50 49 48 46 45 43 42 72 26 25 24 23 22 21 B A 73 75 76 77 78 79 80 GND 15VDC 12VDC IN GND 24VAC IN PRO PRO PRO PRO PRO PRO PRO PRO N L L N 1A 1A 1A 1A I 1A EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 121 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Страница 122: ... mm 90 mm 45 mm X 159 Room temperature sensor S 155 85 mm 60 mm 80 mm 30 mm Snow sensor S 158 78 mm 63 5 mm 32 mm 60 mm EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 122 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Страница 123: ...g Valve Yes Yes Yes Yes No No No No Circulation pump Yes Yes Yes Yes No No No No Smartix Base PRO Supply temperature sensor Mixing valve Yes Yes Yes Yes No No No No Circulation pump Yes Yes Yes Yes No No No No PRO PRO Smatrix Base PRO controller EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 123 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Страница 124: ...Moisture sensor 1 Primary return sensor Mixing valve Yes Yes No No Circulation pump Yes Yes No No Snow and ice sensor Domestic Hot Water Supply temperature sensor Return temperature sensor Mixing valve Yes No Circulation pump Yes No EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 124 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Страница 125: ...EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 125 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Страница 126: ... AB MRY Virsbo Sweden Uponor Corporation www uponor com Uponor reserves the right to make changes without prior notification to the specification of incorporated components in line with its policy of continuous improvement and development ...

Отзывы: