o
utdoor
sensor
The outdoor sensor is mandatory and must always be
installed. Either directly to the Move PRO controller or
via an integrated Uponor Smatrix Base PRO controller. If
a Base PRO controller is integrated to the system, it is a
requirement to connect the outdoor temperature sensor
to the Base PRO controller via a thermostat, registered
as a system device. The thermostat is preferably placed
in a non-public area such as a technical room.
Placement of outdoor sensor
Refer to the installation preparation guidelines (
see
section 4.2 Prepare for installation
), and use the
following guidelines when positioning the outdoor
sensor:
1. Attach the outdoor sensor to the north side of the
building where it is unlikely to be exposed to direct
sunlight.
2. Ensure that the outdoor sensor is placed away from
doors, windows, or air outlets.
N
S
E
W
Connect outdoor sensor to controller
The illustration below shows the outdoor sensor
connected to the controller.
#
16
X-159
S-1XX
To connect an outdoor sensor to the controller:
1. Ensure that the power is disconnected from the
controller.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection
terminal positions.
4. Connect the wires from the outdoor sensor to
terminals 16 and 16 on the controller.
5. Tighten the screws fixing the wires to the connector.