3.CONNECTION
20
3-5. Connecting Analog monitor Output (VOL OUT)
Terminal for out put of a voltage proportional to the sensor input .
Output voltage is approx. 2V per 1mV/V(sensor input).
A8
+
-
External device
Load resistance
2k
Ω
or above
SIG
GND
←
Inside Outside
→
A9
F320
CAUTION
• Since the VOL OUT terminals are not insulated from internal circuits,
use shielded cables for connection with an external device, and carry
out wiring within 2 to 3m.
• Do not short-circuit them. Doing so will cause a failure.
• Do not apply external voltages. Breakage will result.