10.BCD DATA OUTPUT
90
BCD data hold
-
Level input
-
The BCD data output signal is held. (The indicated value is not held.)
It is carried out by pin A14.
When level input is OFF (non-conducting), output signal is hold release.
When level input is ON (conducting), output signal is hold.
Logic Switching
-
Level input
-
Switch the output signal with pin B14.
When level input is OFF (non-conducting), output signal is negative logic.
When level input is ON (conducting), output signal is positive logic.
Hold release
Hold
Undefined section (5ms or less)
OFF
ON
Negative logic
Positive logic
Undefined section (5ms or less)
OFF
ON