5.2. Conditions and indications
When the repeater IFS7002R is switched on it runs an initial verification of CAN network parameters.
It checks the entered fire control panels and their condition.
The repeater IFS7002R operates in seven basic modes: Duty Mode, Fire Condition, Fault Condition,
Disabled Component Mode, Test Mode, Information and Control Mode and SetUp Mode:
Table 1
Condition
Description
Duty Mode
Condition in which the connected remote stations dist.panel not in any
of the other six states and have a relationship with him (see item 6.).
Fire Mode
Condition in a burn in the fire area from a remote fire control panel
connected to the repeater (see item 7.).
Fault Mode
Condition where the fault is in one of the connected remote fire control
panels or dropping the connection to a remote panel (see item 8.)
Disabled Component Mode Remote Panel enters Disabled component after hand surgery to
disable - a fire alarm zone, addressable device, addressable
controllable output or any of the connecting fire control panels.
Test Mode
Condition, after manual operation to place zone from remote fire
control panel in "Test".
Information and Control
Mode
Repeater enters Information and Control Mode of the main menu of
Duty Mode, Fire condition, Fault Mode (without fatal error), Test and
Disabled component (see item 9). In this condition, displays
information about the remote panel and connected fire panels and
control data are entered.
SetUp Mode
The repeater enters setup activation submenu "Setup" from the
Information and Control Mode (see item 10). These may set
configuration repeater parameters.
In any moment the repeater can be in any of the above conditions/modes, or in a random combination
of Fire condition, Fault condition, Disabled component, Test mode and Information and Control mode.
Duty Mode, SetUp Mode and Remote Control Mode can not be combined with another mode:
−
The repeater enters Duty Mode after all other conditions are exited.
−
When the repeater enters SetUp Mode or Remote Control Mode it exits all other
conditions.
The conditions of the repeater and their corresponding indication are shown in Table 2.
Table 2
Conditions of the repeater
Indication
All conditions –
the repeater is power supplied
Indicator
Power supply
–
continuous green light
Fire condition
Common indicator
Fire condition
–
flashing red light
Fault condition
All faults except for
Battery low
Common indicator
Fault condition
– continuous yellow light
Fault condition – System error
Indicator
System error
- continuous
yellow light
Fault condition -
Fault in mains supply
Indicator
Fault in mains supply -
continuous yellow light
Disabled component -
Disabled zone, addressable device or monitored
output
Indicator
Disabled component
-
continuous yellow light