UniPOS Repeater IFS7002R
Instruction Manual Page 15
Revision 2/16.11.09 Of 62
the repeater exits Information and
Control mode and on the display
appear all three panels of the
screen for Fire condition..
7.4. Example
In a network built of 2 repeaters IFS7002R and 5 fire control panelsIFS7002 (Appendix4) have been
reported as a response detectors.
In a fire condition are different zones of the plants in the "Building#2” and "Building#4".
Remote panels IFS7002R, located in the objects “Security” and “Transport gate” are in Fire condition
stage I.
The indication has the following:
- Indicator
(“Fire”) lights blinking
red light.
- The local sounder produces an
intermittent signal (0,5 s sound, 0,5 s
pause).
- Text information:
• Total number of fires - 3;
• First registered in entrance of
Building#2. Phase-fire first. Time left to
fire into stage II - 120 seconds
• Last registered in a corridor 2nd floor
of Building # 4. Phase of fire - first.
Remaining time to fire stage II - 145
seconds.
FIRE CONDITION
ZONES IN FIRE CONDITION: 3
> 1 Phase 1 Zone 001 Building #2
Entrance
3 Phase 1 Zone 002 Building #4
Korridor 2 floor
Time to Phase 2: 120
Time to Phase 2: 145
Devices in fire condition
Total number: 4
1 Loop 01 Zone 001 Addr 001 Object: Building #2
Point 1.001
2 Loop 02 Zone 003 Addr 001 Object: Building #2
Point 2.001
4 Loop 01 Zone 002 Addr 002 Object: Building #4
Point 1.002
Faults total: 00000/0000* Outputs in fault: 00000
Disables total: 000 Disables outputs: 000
• Suppressed message for a fire, occurred between 1 and 3 (numbers visualized fires are not
consistent, ie there is a fire with number 2, whose release is suppressed).
•
Total number of devices in the fire – 4.
•
Positions 1, 2 and 4 describe the specific device in a fire (address, outline, area, etc.).
• Depressed message device in the fire, between devices with serial numbers 2 and 4 (visualized
unit numbers are not consecutive. The display can be seen the first two and last able fire alarm);
The third text window: information introduced disables and faults - in this case there are no disables
and no faults.
Possible actions are:
- If the access level 1:
• View suppressed messages for fire - buttons
(“Move Up”) and
(“Move Down”).
• View suppressed messages for device in fire - buttons
(“Move Up”) and
(“Move Down”).
• Add time intelligence headquarters visualized marker for selection against
>
- button
(“Inspection”).
• Suppression of local sounder - button
(“Stop Alarm”).
- At Access level 2, after entering a password:
• All actions by the access level 1.
• Force removal of connected fire control panel capable of "Fire." Reset only fire panel, visualized
marker for selection „>” - button
(“Reset Fire”) (fire in Building#2 – Entrance).
The repeater remains in Fire condition until all Fire conditions in each of the fire control panels
connected with it is reset .