UniPOS Repeater IFS7002R
Instruction Manual Page 38
Revision 2/16.11.09 Of 62
Mode DAY
REP
14:18:38
Wed 24 Aug 2011
Set Up CAN Parameters Repeater
Name of the repeater: Repeater 001
Address of the repeater: 1
TOut/RecNext,[0.1s]: 30
TOut/RecConf,[0.1s]: 50
TOut/RecResp,[0.1s]: 60
Counter ‘Beep’ function: 0
MaxErrRec: 3
MaxErrSend: 2
Check period,[s]: 5
Rate,[Kbits/s]: 080
Priority communic. level: Subordinate
Total connected CAN objects: 1
2
С
1
0
3 4 5 6 7 8 9
10.4.2.2.2.
Menu
CAN Local parameters
SetUp
(10)
Local Network
(10.4.2.2)
CAN local object name
(10.4.2.2.1)
Network
(10.4.2.1)
Repeater parameters
(10.4.2)
Checks
(10.4.3)
Repeater configuration
(10.4.1)
New passwords
(10.4.4)
Default parameters
(10.4.5)
CAN local parameters
(10.4.2.2.2)
CAN objects
(10.4.2.2.3)
Add new CAN object
(10.4.2.2.3.1)
Del CAN object
(10.4.2.2.3.2)
List/Change CAN object
(10.4.2.2.3.3)
Display
(10.4.3.1)
Buttons
(10.4.3.2)
Level 2
(10.4.4.1)
Level 3
(10.4.4.2)
Options
(10.4.4.3)
The screen serves for entry of CAN
parameters, as on the first line the
name of the repeater is visualized.
The following parameters are entered:
Parameter
Range of the
receiving
values
Default value
of the
parameter
Description
Address of the repeater
0
÷
127
Unique address of the repeater within the
established network
Tout/RecNext,[0.1s]
1
÷
120
30 х 0.1
s=3s
Maximum waiting time for receiving the
next telegram (part) when receiving long
messages.
Tout/RecConf,[0.1s]
1
÷
120
50 x 0.1s=5s
Maximum waiting time for receiving
confirmation after a telegram
–
command/data message not requiring a
response has been sent.
Tout/RecResp,[0.1s]
1
÷
120
60 x 0.1s=6s
Maximum waiting time for receiving a
response after a telegram requiring a
response has been sent.
Counter ‘Beep’ function
0
÷
100
0s
Short signaling of the sounder for the