1: Safety
2
UPS725-02-02 PowerWave 1000 (4.5 - 10 kVA) User Manual UK Dated 13/03/15
1.3
Important safety notes
Although the PowerWave 1000 UPS was designed for simple installation, it must be installed by a suitably qualified
service specialist. The UPS does not contain any user-serviceable parts, so if it malfunctions it must be serviced or
repaired by a trained engineer.
The UPS is equipped with an electromagnetic interference filter (EMI). It must be properly earthed at all times in order to
prevent excessive leakage currents.
To prevent the UPS from overheating, the UPS ventilation louvres on the UPS front panel must be kept free of
obstructions at all times. A space of at least 30 cm (12 in) should be provided at the back of the UPS to allow adequate
airflow from the ventilation fans.
The UPS is must be installed in a sheltered and controlled environment away from direct sunlight. The operating
temperature should be between 0-40°C with relative humidity of 30-90%, non-condensing.
Before installing the equipment you must check to ensure that the UPS input voltage stated on the UPS data-plate on the
back of the unit matches your local utility supply voltage.
The UPS warranty will be rendered void, and the manufacturer reserves the right to refuse replacement or compensation
in the following events:
• Accidental damage to the UPS.
• Ingress of liquids or foreign bodies.
• Damage or malfunction due to installing the UPS in an environment that fail to meet the conditions specified in this
manual.
• Damage or malfunction due to improper installation, configuration or maintenance carried out by an unauthorised
person.
1.4
Storage instructions
If you intend to store the UPS for an extended period, in a moderate climate, the batteries should be charged for 12 hours
every 3 months by connecting the UPS to the utility supply. If the ambient temperature at the storage location is above
30°C, this should be carried out every 2 months.
CAUTION: Please read the following notes carefully prior to installation.