UPS725-02-02 PowerWave 1000 (4.5 - 10 kVA) User Manual UK Dated 13/03/15
47
5: Parallel UPS System Operating Procedures
Note:
If the UPS bypass mains supply is disconnected when it is operating on bypass, the UPS will not revert to battery
power but will instead shut down with a
faIL
status indication. The UPS internal electronics will remain powered from the
battery and all leds will extinguish apart from the red
FAULT
led, which will be permanently lit, and the audible alarm will
sound continuously.
5.3.2 Transferring the load from the static bypass back to the UPS inverter
To transfer the load from the internal static bypass supply (‘
On-bypass
’ mode) to normal operation (‘
On-line
’ mode),
follow the normal start-up procedure in paragraph 5.1, beginning at step 8.