4: Single Module Operating Procedures
40
UPS725-02-02 PowerWave 1000 (4.5 - 10 kVA) User Manual UK Dated 13/03/15
4.2
Operator control functions
At any time during normal operation of the UPS the operator can:
• Monitor the UPS input supply, output supply, battery and internal temperature using the LCD display.
• Enable or disable the audible alarm.
• Functionally test the battery.
4.2.1 Using the LCD metering function
The LCD metering function can display the input voltage, input frequency, load voltage, load frequency, percentage load,
battery voltage and internal temperature. When the UPS is operating, you can scroll through these parameters using the
DOWN
or
UP
button.
Note that the three arrowheads on the LCD mimic diagram identify the source of the meter indication as being either
Input
,
Load
or
Battery.
LINE
UPS
LOAD
V
LINE
UPS
LOAD
Hz
LINE
UPS
LOAD
V
LINE
UPS
LOAD
Hz
LINE
UPS
LOAD
C
LINE
UPS
LOAD
%
LINE
UPS
LOAD
V
Input line voltage
Input line frequency
Load voltage
Load frequency
Load percentage
Battery voltage
Internal temperature
Scro
ll DO
W
N
Scroll
UP