UPS725-02-02 PowerWave 1000 (4.5 - 10 kVA) User Manual UK Dated 13/03/15
31
3: Installation and Set-up
Inverter output voltage
11. Press the
DOWN
button.
a) The LCD indication will now show either
o200
V
,
o208
V
,
o220
V
,
o230
V
or
o240
V
.
12. Press the
UP
button to select the required output voltage.
Input/Output frequency changer mode
The UPS cannot be configured to operate as either a 50/60 Hz or 60/50 Hz frequency changer in a parallel system.
13. Press the
DOWN
button.
a) The LCD indication will now show either
norL
,
Eco
,
c50
Hz
or
c60
Hz
.
14. Press the
UP
button, if necessary, to ensure the frequency is set to
norl
(default).
Inverter output fine adjustment
15. Press the
DOWN
button.
a) By default, the LCD indication will now show
oA 0
%
.
b) If you want to trim the output voltage, press the
UP
button to cycle through the available options and select the
required value –
oA1
%
,
oA 2
%
,
oA 3
%
,
oA-1
%
,
oA-2
%
,
oA-3
%
.
Parallel ID Number
Note:
This is a temporary setting necessary to run the UPS as a single module for functional test purposes before
configuring it as part of a parallel system. This setting will be changed later.
16. Press the
DOWN
button.
a) For a single module operation the parallel ID number must be set to
Id0l
(default).
If this is set incorrectly the UPS LCD will display error message
Er17
when it is started.
Parallel Function
Note:
This is a temporary setting necessary to run the UPS as a single module for functional test purposes before
configuring it as part of a parallel system. This setting will be changed later.
17. Press the
DOWN
button.
a) For a single module operation the parallel function must be set to
P 0l
(default).
If this is set incorrectly the UPS LCD will display error message
Er21
when it is started.
Confirm & Save
18. Press the
DOWN
button.
a) The LCD indication will now show
SAuE
.
b) If you want to double-check all the selected values you can scroll through the above list of parameters by
repeatedly pressing the
DOWN
button and make any necessary further changes.
c) Once you are satisfied that all the selected values are correct, with
SAuE
shown on the LCD display press the
ENTER
button to store the selected values in the UPS memory.
d) The LCD panel will revert to indicate the battery is on charge and UPS is
off
.
Note:
Once the configuration has been saved you must turn
OFF
the UPS and temporarily turn off the input utility
supply before you can access the setup mode again using the
ON
and
DOWN
buttons. This is a safety measure
designed to prevent the UPS operating parameters being changed while it is on-line.
UPS Module functional check
1. Turn
ON
the UPS module as described in paragraph 4.1.1.
2. Check all metered parameters to ascertain that the indications are correct (see page 40) and make a note of the UPS
output voltage.
3. Leave the UPS running for at least 10 minutes to ensure there is some charge in the battery then isolate the UPS
input supply. The UPS should automatically switch to battery operation.
a) The audible alarm should beep (cancel by pressing the
ON
button).
Содержание PowerWAVE 1000
Страница 1: ...PowerWAVE 1000 4 5kVAto10kVASinglePhaseModels UserManual ...
Страница 2: ......