3: Installation and Set-up
34
UPS725-02-02 PowerWave 1000 (4.5 - 10 kVA) User Manual UK Dated 13/03/15
3. Leave the modules in this state for at least 4 hours to fully charge the batteries, then turn on each module in turn
following the instructions given in paragraph 5.1.
Troubleshooting other fault codes that might appear
3.8
UPS Setting Tool
The UPS Setting Tool is a software application that is
supplied with the PowerWave 1000. It enables you to select
certain basic UPS basic operating functions, calibrate the
UPS output voltage, and set-up the module’s single/parallel
operating parameters to make it suitable for either mode of
operation.
The operating parameters can also be set-up from the UPS
control panel, as described in paragraph 3.6 for a single
module installation, or paragraph 3.7.1 for a parallel module
system.
In order to use the UPS Setting Tool you must connect an
RS232 serial cable between the UPS COM port and the
computer on which the application is installed – with the
computer COM port configured as described in paragraph
2.5.1.
Note:
If you are using the application on a laptop that does
not have a serial port, you will require a readily available
USB-to-RS232 serial adapter cable.
Er16
Output parameters setting error:
Cause: One or more parameter settings conflict between each module.
Solution: Check the parameter settings are identical in each module as per paragraph 3.7.1.
Er17
Conflicting ID Number:
Cause (parallel system): Two, or more, modules have the same parallel ID number
Solution (single module): Change the modules’ ID settings so that they are not duplicated (paragraph 3.7.3).
Cause (single module): Parallel function is deselected but module ID number is not
id01
.
Solution (single module): Change the module ID number to
id01
(see page 29).
ER27
Incorrect operating mode selected:
Cause: UPS module is selected to ECO or frequency changer mode.
Solution: Set the UPS operating mode to
norl
(normal).
Er08
DC Bus high level abnormal:
Cause: UPS output voltages not within 1V of each other when run individually.
Solution: Recalibrate UPS output voltages (paragraph 3.7.2).
Cause: Improper installation or parallel communications failure:
Solution: Check parallel settings (paragraph 3.7.3), and cable connections. Then reapply
Er21
check to the system.
Figure 3.14 UPS Setting tool