background image

ULB PROPRIETARY RIGHTS NOTICE

 - This document contains the confidential and proprietary information of ULB. You may not possess, 

use, copy or disclose this document or any information in it for any purpose without express written permission. Neither receipt from any source, 
nor possession of this document, constitutes such permission. Possession, use, copying or disclosure by anyone without express written 
permission of ULB is not authorized and may result in criminal and/or civil liability. 

U:\ILB\5_Technical Manual\TLB-R1000-480-OS_NO ALL\TLB-R1000_480_MANUAL_Rev03.docx 

  

Page 

31

 of 

35

 

CAUTION 
Do  not  pressure  wash  the  inside  component  terminal  compartment  (relay  panel)  as  damage  may 
occur  to  electro-mechanical load  step  relays,  motor  and  control  circuits,  safety  circuits,  and  terminal 
strip wiring. If splashed, ensure entire compartment is dry before covering. 
 
WARNING 
Pressure washing terminal compartment (relay panel) may lead to condensation and promote internal 
arching. 
 

Additional Preventative Maintenance Measures (as required) 

1. The outside surface of the unit should be wiped or blown free of dust and dirt. Careful consideration 
to controls, metering and relay compartment must be taken into account when pressure washing the 
exterior of the enclosure. Ensure air intake and exhaust areas are clean and debris free. Blast or sand 
any noticeable corrosion areas and cover with a suitable paint or coating. 
2. Remove  both  side  access  panels  and  ensure  all  resistor  terminal  connections including  wire,  bus 
jumper are tightened to 15 in-lb and ceramic tubes spring bushings are tightened to 9 in-lb. Inspect all 
ceramic bushings and insulators for cracks. Replace all broken or cracked ceramic insulators. Ensure 
all  fan  and  safety  component  connections  are  tight.  If  required,  it  is  safe  to  blow  any  dust  from  this 
compartment  using  40  PSI  or  less  of  clean,  dry,  compressed  air.  Replace  any  broken  or  failed 
components. Reinstall access panel cover before proceeding with any enclosure maintenance. 
3.

 

If resistor elements are extremely dirty, elements can be pressure washed. Pressures up to 40PSI 

at a distance of two feet or greater may be used when cleaning the resistor elements. Pressure should 
be reduced for the connection points and the distance from the nozzle to any insulator should not be 
closer than four feet to prevent damage. 
 

WARNING  

  Disconnect  all  sources  of  power  to  the  unit  (Main  input  Load  Bus,  external  Blower  Power, 

External  Control  Power)  prior  to  any  inspection,  service,  or  cleaning.  Electric  Shock  Hazard 
exists while connected.  

  For corrections requiring repair or replacement of components, contact the factory immediately 

for further instruction.  

  Only those functions within the scope of normal maintenance are listed. This manual cannot list 

all  malfunctions  that  may  occur,  or  corrective  actions.  If  a  malfunction  is  not  listed  or  is  not 
corrected by listed corrective actions, notify the factory.  

Note: When checking fuses for continuity, remove all fuses from fuse blocks, bus bars, fuse holders, 
and disconnect switch. Test each fuse individually and out of circuit. A blown fuse left in the circuit may 
check out OK with false reading of continuity due to feedback and return paths within the circuit. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание TLB-R1000-480-OS

Страница 1: ...ession use copying or disclosure by anyone without express written permission of ULB is not authorized and may result in criminal and or civil liability U ILB 5_Technical Manual TLB R1000 480 OS_NO AL...

Страница 2: ...sclosure by anyone without express written permission of ULB is not authorized and may result in criminal and or civil liability U ILB 5_Technical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_R...

Страница 3: ...Page 3 of 35 ABBREVIATIONS AND ACRONYMS The following is a list of abbreviations and acronyms used throughout this manual A Amperes Amps AC Alternating current AI Analog Input AO Analog Output CMM Com...

Страница 4: ...AY FROM LIVE CIRCUITS 5 SHOCK HAZARD 5 DO NOT SERVICE OR ADJUST ALONE 5 SAFETY EARTH GROUND 5 CHEMICAL HAZARD 5 EMERGENCY AID 5 POTENTIALLY HAZARDOUS OPERATOR CONDITIONS 5 EMERGENCY SHUT DOWN 6 SAFETY...

Страница 5: ...Do not replace components or make adjustments to equipment with power turned on To avoid casualties always remove power to the entire system Turn off and disconnect the main power source under test D...

Страница 6: ...ime after operation as these surfaces become hot and may result in a serious burn injury Never bypass any blown fuse Replace any indicator lamps on the operator control panel as required Each indicato...

Страница 7: ...he following safety warnings appear in the text where there is danger to operating personnel They are noted and repeated here for emphasis WARNING Disconnect unit from all power sources before any dis...

Страница 8: ...should occur after receiving the unit Periodic preventative maintenance and inspections should be performed to ensure system reliability Upon receipt of your Load Bank be sure to carefully unpack the...

Страница 9: ...be used without the Fan Blower Motor operating Inadequate cooling airflow will result in resistor load elements overheating fire hazard and danger to personnel Operating Instructions General All insta...

Страница 10: ...e NEC National Electric Code or any local codes Correctly sized copper compression lugs are recommended The Load Bank has three main input load bus bars marked L1 L2 and L3 Load cable connections are...

Страница 11: ...L TLB R1000_480_MANUAL_Rev03 docx Page 11 of 35 Use HMI display touch screen to set require KW Minimum KW resolution that can be selected is 25KW Set desired time duration in Hours HR and Minutes MIN...

Страница 12: ...ocx Page 12 of 35 Safeties Any alarm condition existing in the load bank is indicated by LOAD BANK SAFETY NOT OK indication on the top right corner of the main screen on HMI To investigate safety NOT...

Страница 13: ...wer E stop Loss of control power or E stop is operated Table 1 All load steps are disabled and load cannot be applied unless all above parameters in OK status Green Color Note Ensure and check for pro...

Страница 14: ...riminal and or civil liability U ILB 5_Technical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 14 of 35 Power data 1 Power data display Click POWER DATA button on main screen and...

Страница 15: ...inal and or civil liability U ILB 5_Technical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 15 of 35 WARNING While Load bank is running with load applied condition setting Load D...

Страница 16: ...l liability U ILB 5_Technical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 16 of 35 Load Profile Using this feature load bank can be configured to operate at various load condit...

Страница 17: ...Fig 5 Load Profile 3 Enter require Hr Min and KW values for each step and click ACTIVATE button a Now Load bank will start operating with Hr Min and KW values selected for step 1 This will be indicate...

Страница 18: ...hnical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 18 of 35 e Load bank will continue to operate at KW values Hr and Min selected for step 1 then after step 2 will be activated...

Страница 19: ...al and or civil liability U ILB 5_Technical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 19 of 35 Operating Multiple Load banks Multiple load banks Max 5 can be operated in Mast...

Страница 20: ...screen shown below Refer maintenance section below to know how to access this screen on the display 1 Each Load bank should have unique ID anywhere from 1 16 assigned 2 The First load bank in the net...

Страница 21: ...bank should have following settings in above screen THIS LOAD BANK TO OPERATE AS SLAVE THIS LOAD BANK ID 4 Tip Next higher number from Slave 2 Load bank ID ID OF SLAVE 1 LOAD BANK Not applicable Slav...

Страница 22: ...03 docx Page 22 of 35 Powering up Master Slave Load banks Note For master to identify all salves load banks master load bank should be powered up last i e power up all slave load banks first or all lo...

Страница 23: ...permission Possession use copying or disclosure by anyone without express written permission of ULB is not authorized and may result in criminal and or civil liability U ILB 5_Technical Manual TLB R10...

Страница 24: ...l TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 24 of 35 WARNING Load bank should never be operated in Master Slave mode if any of the COMM Communication status indicator on above scree...

Страница 25: ...Page 25 of 35 Data Logging 1 Insert USB stick in USB port on the back of HMI display 2 Click DATA LOGGING button will show following screen See Fig 11 Fig 11 Data Logging 1 Click START LOGGING will s...

Страница 26: ...closure by anyone without express written permission of ULB is not authorized and may result in criminal and or civil liability U ILB 5_Technical Manual TLB R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Re...

Страница 27: ...circuits WARNING DO NOT touch the exhaust louver during operation Hot Air exhaust will cause serious burns DO NOT allow objects to enter or block air intake or exhaust louvers DO NOT operate the Load...

Страница 28: ...his load bank WARNING Stop Load Test before entering in to this set up screen Setting should be changed by only qualified person who clearly understands implication of changing each setting A pop up w...

Страница 29: ...injury from electrical shock or from moving fan blades could result unless all sources of power are completely disconnected before servicing Maintenance must always be done by qualified technician Ma...

Страница 30: ...ened and elements are clear and free of debris 6 Inspect all resistors for mechanical and structural integrity and location Replace any excessive sagging resistor elements ceramics and support rods Re...

Страница 31: ...jumper are tightened to 15 in lb and ceramic tubes spring bushings are tightened to 9 in lb Inspect all ceramic bushings and insulators for cracks Replace all broken or cracked ceramic insulators Ensu...

Страница 32: ...ng coil or on operator control unit main power blower start stop pushbuttons Blower Motor fuse is blown check and replace as required Motor Over Load relay is tripped Motor starting relay failed Fan b...

Страница 33: ...nnot be energized Blower Failure Air failure Over Temp Wrong Voltage Motor Overload Load Dump see item 2 thru 8 above Load Dump switch is operated One or more of the branch circuit load step fuses for...

Страница 34: ...f time indoors cover the unit to prevent any accumulation or buildup of dust or dirt If stored outdoors do not cover with plastic that may create condensation and enclosure corrosion or staining keep...

Страница 35: ...R1000 480 OS_NO ALL TLB R1000_480_MANUAL_Rev03 docx Page 35 of 35 Customer Service Any maintenance or service procedure beyond scope of those provided in this manual should be referred to a factory en...

Отзывы: