Operating Multiple Load banks
Multiple load banks (Max. 5) can be operated in ‘Master – Slave’ mode by connecting load
banks in daisy chain networking as shown below (See Fig.6)
Fig.6 Master Salve connection
Note:
1) Maximum 5 Load banks can be connected in Master – Slave mode. So, for load bank
with 1000KW each capacity, multiple load bank operation will provide maximum 5 x
1000KW = 5000KW capacity.
2) Example shown here is for 1000KW load banks. KW Capacity and settings will vary
depending on individual load bank KW capacity i.e. 1000KW, 750KW or 500KW.