THIS LOAD BANK TO OPERATE AS “SLAVE”
THIS LOAD BANK ID
2
(Tip: Next higher number from Master Load bank ID)
ID OF SLAVE 1 LOAD BANK
Not applicable
Slave 2 (Next to Slave 1 Load bank) should have following settings in above screen,
THIS LOAD BANK TO OPERATE AS “SLAVE”
THIS LOAD BANK ID
3
(Tip: Next higher number from Slave 1 Load bank ID)
ID OF SLAVE 1 LOAD BANK
Not applicable
Slave 3 (Next to Slave 2 Load bank) should have following settings in above screen,
THIS LOAD BANK TO OPERATE AS “SLAVE”
THIS LOAD BANK ID
4
(Tip: Next higher number from Slave 2 Load bank ID)
ID OF SLAVE 1 LOAD BANK
Not applicable
Slave 4 (Next to Slave 3 Load bank) should have following settings in above screen,
THIS LOAD BANK TO OPERATE AS “SLAVE”
THIS LOAD BANK ID
5
(Tip: Next higher number from Slave 3 Load bank ID)
ID OF SLAVE 1 LOAD BANK
Not applicable
Physical connection
1) Each load bank has one input port (PORT-1, E305A) and one output port (PORT-2,
E306A) located just below display assembly on the load bank.
2) Master load bank will have no connection on the input port. Connect networking cable
(E611A) from output port of Master load bank to the input port of next load bank
(Slave-1). Similarly, connect networking cable from out port of Slave-1 load bank to
input port of Slave-2 Load bank. Connect Slave-3 and Slave-4 in similar way.
3) Make sure network resistor (E612A), located on TB1 inside each load bank are placed
in line for Master and last slave in the network e.g Slave-4. However this network
resistor must be pulled out for any load bank between Master and last slave e.g from
Salve-1, Slave-2 and Slave-3