Use HMI display touch screen to set require KW. Minimum KW resolution that can be selected
is 25KW. Set desired time duration in Hours (HR.) and Minutes (MIN.) for which selected KW is
to be applied.
Click <LOAD APPLY> button on Main Screen. This action will start cooling fan and the
preselected amount of load KW will be applied to the power source under test.
Any available combination of incremental KW load values can be turned ON/OFF during operation to
achieve the desired load on the power source under test.
Also, When set time duration is over, load will automatically disconnect and cooling fan will continue to
run for pre-set cooling time of 5 minutes (OR as set in the Maintenance screen)..