background image

IM_ONE_Safety-07

www.ueonline.com

6

The One Series 

Field Safety System™

 enclosure includes two conduit openings, 

one intended for the high-power SAFETY RELAY OUTPUT (SRO) wiring and the 

other intended for low-level signal and analog 4-20 mA wiring.  4-20 mA signals 

shall be wired using a shielded/twisted pair to minimize the effects of electrical 

interference.  Please follow local electrical code requirements for explosion/flame 

proof instrumentation.

The diagrams in Figures 5 and 6 provide a rear view of the display module after 

it has been removed from the base enclosure and an inside view of the base 

enclosure circuit boards.  Terminal Block 1 (TB1) is located on the display module.  

All other terminal blocks (TB2 - TB4) are located inside the base enclosure.

Model 2SLP is loop-powered and is connected directly to an analog input of a PLC 

or DCS via TB1 providing a 4-20 mA analog signal (see Table 3). (Polarity must 

be observed).  The loop connection powers the entire One Series 

Field Safety 

System™

, including the Safety Relay Output switch actuation.  The auxiliary SAFETY 

RELAY OUTPUT is connected via TB2 and is intended to switch an external load.  

Refer to Table 3 for the SAFETY RELAY OUTPUT switch ratings.

Figure 6 shows the switch wiring connections located at TB2, TB3 and TB4 inside 

the base enclosure. TB2 A and B terminals are provided for the external power 

supply inputs to be switched by the Safety Relay Output. The SRO at TB2 C and D 

terminals provide connections to the Safety Relay Output switch. Polarity must be 

observed on all VDC switches.  Please refer to the wiring diagrams shown on page 

7. 

The SRO Monitor function, if used, requires a connection to VDC (+) or VDC (-) 

depending on whether the SRO circuit arrangement is sinking or sourcing (either 

Neutral1 or Neutral2 for model 2SLP47). This connection allows the SRO current 

to be measured that is sent out to an external load (final element), allowing the 

IAW

TM

 diagnostics to determine the integrity of the SRO wiring and if the SRO is 

functioning properly.

NOTE:

 As an alternative to loop power, model 2SLP may be wired directly to a 

24 VDC power supply (+) and minus (-) terminals.  In this wiring configuration, 

power is provided for all switching and diagnostic functions but a 4-20 mA output 

is not possible.  This alternative method of powering the One Series 

Field Safety 

System™

 may be used when loop power is not available and a 4-20 mA output is 

not desired.

Two additional discrete outputs are available at TB3 and TB4 - SRO STATUS and 

IAW OUTPUT.  These are intended for use in Safety Instrumented Systems (SIS) 

applications and for monitoring certain One Series Safety Transmitter functions.  

These discrete signals are useful for voting logic schemes where the safety PLC can 

decide to initiate an emergency shutdown (ESD) or an alarm depending on their 

state.  These outputs may also be used to distinguish between a process upset 

(set point reached) or the IAW™

 

self-diagnostics detecting a fault with the One 

Series 

Field Safety System™

.  Please refer to table 4 on page 15 for additional 

information.

NOTE:

 Do not exceed the maximum switch ratings of the SAFETY RELAY OUTPUT, 

IAW™ OUTPUT and SRO STATUS signals or permanent damage to the One Series 

Field Safety System™

 may result.  Please refer to Table 3.

WIRING DIAGRAMS - MODEL 2SLP

+

+

TB 2

+

-

RED

TB1

+

+

TB4

TB3

TB 2

TB2

TB 2

TB4

TB3

TB 2

SRO/SWITCH STATUS

TB2

IAW OUTPUT

SAFETY

RELAY

OUTPUT

+TB4-2

-TB4-1

+TB3-2
-TB3-1

NEUTRAL 1

NEUTRAL 2

LINE

SRO

Table 3 – Voltage and Current Maximum Ratings

Signal Name

Location

2SLP47

2SLP48

2SLP49

Power Supply

TB1: + & -

2-wire 20-40 VDC @ 4-20 mA (Loop or Fixed Current)

Safety Relay Output

TB2: C & D

12-250 VAC @ 5 mA-5 A

1

0-30 VDC @ 6 A

1

, 1.8 A

1

 Pilot Duty 0-130 VDC @ 2.5 A

1

, Q150

1,2

 Pilot Duty

With Relay Monitor Enabled

12-250 VAC @ 5 mA-5 A

1

10-30 VDC @ 5 mA-6 A

1

10-130 VDC @ 5 mA-2.5 A

1

Temperature Derating

1

1% per ˚C above 25˚C

SRO Status

TB3: 1 & 2

30 VDC @ 20 mA

IAW Output

TB4: 1 & 2

30 VDC @ 20 mA

2

Q150 Pilot Duty: 2.5 A (Continuous Current), 0.55 A (Make or Break), 69 VA

Figure 5 - Rear View Display Module

Figure 6 - Inside View Base Enclosure

Содержание Field Safety System One Series

Страница 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Страница 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Страница 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Страница 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Страница 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Страница 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Страница 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Страница 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Страница 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Страница 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Страница 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Страница 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Страница 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Страница 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Страница 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Страница 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Страница 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Страница 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Страница 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Страница 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Страница 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Страница 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Страница 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Страница 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Отзывы: