PART III - PROGRAMMING
Basic Programming

Tools Required: 

Programming Flowchart (see Flowchart 1, page 19) 

Programming of the One Series 

Field Safety System™

 is accomplished using the two buttons on the faceplate (labeled 

2

 and 

g

 

see Figure 15).  Stepping down through the main menu using the left 

2

 button, you can access the various commands of the software 

menu.  The right button is then used to move into the command submenu for setting up or modifying the parameters. 

NOTE:

  The flowchart on page 19 shows the enitre programming commands menu structure.  Before removing the enclosure cover, 

please read the instructions on page 5.  The programming menu is a single direction lop, with submenus embedded within, so there is 

no way to back up in the program.  If you need to make a correction to a prior Main Menu step, you will need to continue forward, exit, 

then re-enter the program to step through to the appropriate feature.  If you are in a Submenu, you will need to continue to the begin-

ning of the menu item and re-enter the Submenu to make the correction.

Entering the Programming Mode
NOTE:

 While in the Programming Mode, the One Series 

Field Safety System™

 will remove itself from service (go offline).  All out-

puts are set to the fail safe state and the 

Field Safety System™

 ignores process variable input from the process sensor.  The Safety 

Relay Output and Status, and the IAW™ Output signal will open.  The control system will interpret these signals as a detected fault and 

a process upset (set point reached) simultaneously.  

It is essential to alert the control system operators before entering the 

Programming Mode.

  

Use the Flowchart on page 19 as a guide through the various commands in the Programming Mode.

•  Press and release both buttons 

2g

 simultaneously and then press the right button 

g

 to enter the password.

•  Enter the 4-digit password.  The factory defualt password is “0000”.

•  The left 

2

 button increments the blinking digit.  

•  The right 

g

 button sets the digit and moves to the next. 

•  Once a valid password is entered, “OK” will appear on the display. 

•  Press and release the right 

g

 button.  

•  CLR MAX/MIN (or MAN RSET if Latch is set) will appear on the display.  

This is the first command prompt in the Programming Mode.

 

NOTE:

 

The 

Field Safety System™

 will automatically exit the Programming Mode and resume monitoring the process (go back online) 

if two minutes elapse without a button being pressed.  The One Series recalls all previously saved parameters from memory and any 

program changes that were made will be discarded.  This two-minute timeout feature prevents the One Series from being left offline 

accidentally. 

Exiting the Programming Mode

When any of the programming commands are displayed, it is possible to escape and exit the Programming Mode by pressing the left 

2

 and right 

g

 button simultaneously.  Doing this redirects the program to the Save Changes menu location, which is only possible at 

menu actions indicated by an asterisk (*) on the Programming Flowchart, found on page 19. 

NOTE: 

It is also possible to exit the Programming Mode by repeatedly pressing the left 

2

 button from any programming command until 

the Save Changes menu location is reached.

Saving Programming Changes

When changes have been made to the programming settings, a choice is provided to Save or Discard the changes.  At any prompt: 

•  Press both left 

2

 and right 

g

 buttons to display SAVE CHNG menu.

To Save changes, press the right 

g

 button. NO (the default) will be displayed.  

•  Press the left 

2

 button to toggle and display YES. 

•  Then press both left 

2

 and right 

g

 buttons to confirm, save the changes and return to the Process Display mode.  

The One Series will resume process monitoring (go back online) using the new programming parameters.

To Discard changes, press the right 

g

 button. NO will be displayed.

•  Press both left 

2

 and right 

g

 buttons to confirm, discard changes and return to the Process Display mode.  

The One Series will resume monitoring the process (go back online) recalling all previously saved parameters from memory.

Figure 15

Содержание Field Safety System One Series

Страница 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Страница 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Страница 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Страница 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Страница 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Страница 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Страница 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Страница 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Страница 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Страница 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Страница 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Страница 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Страница 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Страница 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Страница 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Страница 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Страница 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Страница 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Страница 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Страница 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Страница 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Страница 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Страница 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Страница 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Отзывы: