background image

IM_ONE_Safety-07

www.ueonline.com

3

I Am Working (IAW™) 

The One Series 

Field Safety System™

 also contains UE’s patented IAW™ self-diagnostic software.  On a continuous basis, the IAW™ algorithm 

checks for proper operation, and locally reports the status using messages or revolving arrows on the display.  For remote reporting, a discrete 

IAW™ output signal can be monitored by logic solver and used to detect normal, tripped, and fault conditions. A discrete outputs truth table is 

provided on page 18.  IAW™ self-monitors, searching for possible faults, both within the instrument and in the overall system (a list of the various 

fault codes is outlined in table 5, page 17). I

n the event of a fault condition, the One Series 

Field Safety System™

 will attempt to display the problem and 

provide remote indication signals using the IAW Status and NAMUR NE43 standard 4-20 mA outputs.  In the case of certain micro-controller faults, the revolving 

arrows may freeze or go out, indicating that a failure exists.  If loop power is interrupted to the One Series 

Field Safety System™

, the display will go blank 

and all discrete outputs will open.

DISPLAY FEATURES AND DIAGNOSTICS

The One Series 

Field Safety System™

 features a large, easy to read LCD display (See Figure 1).  It is used for three main purposes:  process 

indication, programming and switch status/troubleshooting.
In the Process Display mode, the display may be indicating the following:

•  Current process value and units of measure:  A value will be displayed as long as the reading is within 103% of the full    

 

scale range noted on the nameplate.  For valves beyond 103% of range, the PV is replaced with a scrolling message OVER RANGE.

•  I Am Working (IAW

) status:  When the unit is working properly, a circular 4-segment arrow will be revolving around the letters “IAW™” in 

the top center of the display. 

•  Offset/Span Adjustment:  The word “offset” will appear above the process value, indicating that the factory offset and/or span 

calibration has been modified by the user.  

In addition, the user can easily access information such as the set point, deadband and minimum/maximum process readings: 

 

By pushing the right 

g

 button once, the display will scroll as follows:

   

SP1   XX.XX    DB1   XX.XX  SP2   XX.XX   DB2   XX.XX 

 

By pushing the left 

2

 button once, the display will scroll the min/max process values recorded in memory:

  

 

 

 

MAX   XX.XX    MIN   XX.XX

The display will automatically revert back to the Process Display mode after scrolling

.

ALARM CONDITION

When the process goes beyond the set point, the display will begin to flash, alternating between the process value and “SW1”.  This indicates that 

set point has been reached, causing the Safety Relay Output (SRO) and Status Switches to open.  The display will continue to flash until the process 

has returned to a value beyond the deadband, at which point the display will revert to normal operation and process value display.  If the unit was 

programmed to have a latching output, a small “Latch” icon will light in the display when the set point is reached, indicating that the output is 

latched and needs to be manually reset.  

FAULT CONDITIONS

In the case of a fault condition, the display may indicate the following:

•  If the IAW software detects a fault it will display an error code and force the SRO, SRO Status and IAW Outputs to open state and the 4-20 mA output to the 

fault current.

•  If the power supply or the wiring fails, the display will go blank.  All switch outputs will open (fail safe open) and the 4-20 mA signal will go to zero.

(See the Fault Codes and the Discrete Output Truth Table on pages 17 and 18 for a complete description of fault diagnostics and the response by the One Series 

Safety Transmitter.)

Please refer to the product technical brochure for product specifications.  Product technical brochure may be found at www.ueonline.com.

UE declarations and third party issued certifications are available for download at www.ueonline.com/support/certifications/.

Date code format on nameplate is “YYWW” for year and week (see Figure 19, Page 18)

PART I - MOUNTING

Tools Required: 

Screwdriver for mounting bolts; 4 mounting bolts (1/4” Max.)

NOTE

: For optional surface and pipe mounting kit, order part no. 6361-704.  See page 20

.

BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE SENSOR 

AND WETTED PARTS.

IN ALL APPLICATIONS, SECURE THE ENCLOSURE AS DETAILED BELOW. DO NOT MOUNT VIA THE PROCESS CONNECTION ONLY. 

Figure 1

Содержание Field Safety System One Series

Страница 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Страница 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Страница 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Страница 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Страница 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Страница 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Страница 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Страница 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Страница 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Страница 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Страница 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Страница 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Страница 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Страница 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Страница 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Страница 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Страница 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Страница 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Страница 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Страница 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Страница 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Страница 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Страница 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Страница 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Отзывы: