background image

IM_ONE_Safety-07

www.ueonline.com

13

ADVANCED FEATURES

NOTE:

  No initial configuration of these features is required.  The default for these advanced commands is zero or off.

Adjusting Display Offset

The One Series 

Field Safety System™

 is factory calibrated to 0.25% of the sensor’s maximum range at room temperature.  In some 

installations, it may be necessary to adjust the display’s offset due to the range and position of the sensor.  Chemical seals with long 
capillaries combined with low maximum range sensors are a common cause of offset error.  The OFFSET command allows the user 
to enter a positive (“POS”) or negative (“NEG”) offset to the display readings.  An offset adjustment of up to +10% of the sensor’s 
maximum range is allowed.  If adjusting OFFSET, it may be necessary to adjust SPAN (see below).
Example: When the sensor has a zero pressure applied, but the display reads a value other than zero, entering the additive inverse 
(reversing the sign) of the displayed value for OFFSET will force the display to read zero.

NOTE:

  Any numerical value entered other than 0.00 will cause the display to indicate “Offset” just above the process reading in the 

process display.

USE OF THIS OPTION MAY CREATE A CONDITION WHERE THE DISPLAY MAY INDICATE “0.00” WHEN SIGNIFICANT PRESSURE OR 

TEMPERATURE (UP TO 10% OF MAXIMUM RANGE) EXISTS IN THE SYSTEM.  INDEPENDENT VERIFICATION OF THE PROCESS VARI-

ABLE SHOULD BE DONE PRIOR TO MAINTENANCE ON THE SYSTEM WHEN “OFFSET” APPEARS ON THE DISPLAY.

Refer to the Programming Flowchart on page 19.
•  Enter the Programming Mode and use the left 

2

 button to move to the OFST command.

•  Press the right 

g

 button to select a positive or negative offset.  POS is default.  Use the left 

2

 button to change to NEG.

•  Press the right 

g

 button to view and change the offset.  Zero is the factory setting.  Press the left 

2

 button to increment the blink-

ing digit.  Press the right 

g

 button to enter and move to the next digit.

•  Press the right 

g

 button to enter the new offset and return to the main menu.  

Adjusting Span

SPAN provides an adjustment to shift the slope of the sensor’s response curve to accommodate an offset value other than zero.  To 
adjust SPAN, calculate and enter a new SPAN value. 

To calculate the SPAN value, apply a reference source below maximum scale to the sensor.  Record the value that shows on the One 
Series 

Field Safety System™

 display and the reference source value.  Divide the reference source value by the display value and then 

multiply the result by the sensor’s upper range.

FORMULA: SPAN = reference source / display value x upper range value
•  Pressure example: For a sensor range of 0 - 100 psi, choose a reference source (90) below the upper range limit (100) to 

prevent an over range condition. Divide the reference source value from the resulting display value (88).  Multiply the result by the 
upper range limit.          Span = 90 / 88 x 100 = 102 (rounded)

•  Temperature example: For a sensor range of -40 to 450ºF, choose a reference source (400) below the upper range limit (450) to 

prevent an over range condition.  Divide the reference source value from the resulting display value (404).  Multiply the result by 
the upper range limit.   Span = 400 / 404 x 450 = 446 (rounded)

Refer to the Programming Flowchart on page 19.

•  Enter the Programming Mode (see page 10) and use the left 

2

 button to move to the SPAN command. 

•  Press the right 

g

 button to select a positive or negative span.  POS is the default.  Use the left 

2

 button to change to NEG.

•  Press the right 

g

 button to view and change the span.  Zero is the factory setting.  Press the left 

2

 button to increment the blink-

ing digit.  Press the right 

g

 button to enter and move to the next digit.

•  Press the right 

g

 button to enter the new span and return to the main menu.

Содержание Field Safety System One Series

Страница 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Страница 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Страница 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Страница 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Страница 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Страница 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Страница 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Страница 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Страница 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Страница 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Страница 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Страница 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Страница 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Страница 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Страница 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Страница 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Страница 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Страница 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Страница 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Страница 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Страница 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Страница 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Страница 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Страница 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Отзывы: