background image

IM_ONE_Safety-07

www.ueonline.com

4

Mount the device using the four (4) 1/4” clearance holes in the enclosure base. Plumb sensor to the process port.  See page 20-21 for dimensions.
The device may be mounted in any position except with the sensor connection facing up. Ensure the process connection is sealed to the process 
port to prevent leakage.  Care should be taken to minimize effects of shock and vibration. The One Series should be protected from direct sunlight 
and rain in outdoor installations using a shroud (user supplied).  

NOTE

: the optimal display viewing position is 6:00.

FOR PRESSURE AND LOCAL TEMPERATURE MODELS ALWAYS HOLD A WRENCH ON THE SENSOR HOUSING HEX WHEN MOUNTING DEVICE. DO 

NOT TIGHTEN BY TURNING ENCLOSURE, THIS WILL DAMAGE THE CONNECTION BETWEEN THE SENSOR AND HOUSING.

FOR DIFFERENTIAL PRESSURE MODELS (ESPECIALLY LOW RANGE MODELS), MOUNT THE SENSOR LEVEL TO MINIMIZE ANY PRESSURE 

READING OFFSETS.  THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY, (SEE PAGE 13 FOR ADDITIONAL INFORMATION).

PROCESS CONNECTIONS AND SENSOR INSTALLATION

NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING.  DAMAGE TO THE SENSOR WILL RESULT, AFFECTING ACCURACY.

Pressure and Differential Pressure Models

To pipe mount:  Thread the pressure connection onto the pressure port, with thread sealant, making sure that the mating threads are clean and 

free of debris.  Use a wrench on the pressure connection hex to tighten. Test for leaks.  On Differential Pressure models, the Low (L) side pressure 

must NOT exceed the high (H) side pressure.  Damage to the sensor may result.

Local and Remote Temperature Models

For Local Ambient Sensing (model L):  Mount using the mounting holes on the electronics housing.  Mount the device to ensure that the sensor 

housing will not be damaged and where the measured temperature is representative of the surrounding environment.

For Local Spring-Loaded (model T):  A suitable thermowell, made from corrosion-resistant material, 5 threads engaged minimum, with thread 

sealant, is required to maintain enclosure type 4X/IP66.

For Remote Sensing:  Route the extension wire to avoid contact with live components or close proximity to electrical noise sources. Avoid kinks, or 

excessive flexing. Tighten the ferrule fitting, if applicable.

For Surface Sensing:  Secure the sensor housing to the pipe or vessel using an adhesive or strapping method suitable for the application. 

For Immersion Sensing (models C, H, R & L):  Use of a thermowell is highly recommended to aid in maintenance, testing and preservation of the 

system integrity.  

For existing thermowells with 0.375” bore, an insert is available from UE as part number 62169-44 (see Figure 2).  The adapter provides a 

faster heat transfer by adapting the 0.250” diameter temperature sensor housing to a larger bore 0.375” thermowell.  Heat transfer compound is recommended 

in the bottom of the well and inside the adapter opening.

Insert the sensor housing (0.25” diameter) into the well ensuring that the sensor’s sheath bottoms out and the well is completely immersed in 

the media (2.5” min.) Screw the sensor’s nipple into the thermowell, with thread sealant, by placing a wrench on the union nut. Tighten the union 

connector.

For best temperature measurements, the sensor housing must be in full contact with the surface or media being measured.  Heat transfer compound 

may be used to aid in fully transferring the media temperature to the sensor housing. Locate where the temperature is most representative of the 

system.  Minimum insertion depth is 2-1/2”.  Sensor dimensional drawings are shown on page 21.

  0.375 REF 

0.250

REF

2.50

REF

SENSOR

THERMOWELL ADAPTER

[6.35] mm

[63.5] mm

[9.53] mm

Figure 2

Содержание Field Safety System One Series

Страница 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Страница 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Страница 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Страница 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Страница 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Страница 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Страница 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Страница 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Страница 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Страница 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Страница 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Страница 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Страница 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Страница 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Страница 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Страница 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Страница 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Страница 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Страница 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Страница 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Страница 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Страница 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Страница 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Страница 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Отзывы: