Power Supply and Load Limits

Rmin
Rmax

V

in

R

min

R

max

20

0.0

181.8

21

0.0

227.3

22

0.0

272.7

23

0.0

318.2

24

0.0

363.6

25

47.6

409.1

26

95.2

454.5

27

142.9

500.0

28

190.5

545.5

29

238.1

590.9

30

285.7

636.4

ONE SERIES 4-20mA POWER SUPPLY AND LOAD LIMITS

V

in

R

min

R

max

31

333.3

681.8

32

381.0

727.3

33

428.6

772.7

34

476.2

818.2

35

523.8

863.6

36

571.4

909.1

37

619.0

945.5

38

666.7

1000.0

39

714.3

1045.5

40

761.9

1090.9

No Fault Displayed

4-20 mA Normal Operating range

Unused

Fault < 3.6

3.8 mA Normal 
Under-range

4

20

20.5 mA Normal 
Over-range

21.0 mA*

*21.0 mA only when the temperature 
sensor is subject to 103.25% to 110% 
of range or when the pressure sensor 
is subject to 103.25% to 150% of 
range.

Fault

0

FAULT CURRENT

In addition to the discrete IAW™ and Safety Relay Output status signals, the One Series 

Field Safety System™

 includes a 4-20 mA output that 

adheres to the NAMUR NE 43 current level standard.  Figure 14 deatails these current levels and what they indicate.

A diagnostic fault will force the IAW™ Safety Relay Output and Status to the fail safe state and the (≤ 3.6 mA) fault condition.

Table 4

Graph 1

Figure 14

Содержание Field Safety System One Series

Страница 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Страница 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Страница 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Страница 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Страница 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Страница 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Страница 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Страница 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Страница 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Страница 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Страница 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Страница 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Страница 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Страница 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Страница 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Страница 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Страница 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Страница 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Страница 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Страница 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Страница 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Страница 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Страница 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Страница 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Отзывы: