Power Supply and Load Limits
Rmin
Rmax
V
in
R
min
R
max
20
0.0
181.8
21
0.0
227.3
22
0.0
272.7
23
0.0
318.2
24
0.0
363.6
25
47.6
409.1
26
95.2
454.5
27
142.9
500.0
28
190.5
545.5
29
238.1
590.9
30
285.7
636.4
ONE SERIES 4-20mA POWER SUPPLY AND LOAD LIMITS
V
in
R
min
R
max
31
333.3
681.8
32
381.0
727.3
33
428.6
772.7
34
476.2
818.2
35
523.8
863.6
36
571.4
909.1
37
619.0
945.5
38
666.7
1000.0
39
714.3
1045.5
40
761.9
1090.9
No Fault Displayed
4-20 mA Normal Operating range
Unused
Fault < 3.6
3.8 mA Normal
Under-range
4
20
20.5 mA Normal
Over-range
21.0 mA*
*21.0 mA only when the temperature
sensor is subject to 103.25% to 110%
of range or when the pressure sensor
is subject to 103.25% to 150% of
range.
Fault
0
FAULT CURRENT
In addition to the discrete IAW™ and Safety Relay Output status signals, the One Series
Field Safety System™
includes a 4-20 mA output that
adheres to the NAMUR NE 43 current level standard. Figure 14 deatails these current levels and what they indicate.
A diagnostic fault will force the IAW™ Safety Relay Output and Status to the fail safe state and the (≤ 3.6 mA) fault condition.