Connection
Connection – synchronization mode
20
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Connection diagram of the master sensor in multiplex mode
Pin
Pin assignment
Pin 1
+24 VDC
4 BK
1 BN
3 BU
2 WH
5 GY
Pin 2
Output 2 (analog output or switching output)
Pin 3
GND
Pin 4
Multiplex output, connected to pin 5 of the slaves
Pin 5
Not connected (n. c.)
Pin
Pin assignment
Pin 1
+24 VDC
4 BK
1 BN
3 BU
2 WH
5 GY
Pin 2
Output 2 (analog output or switching output)
Pin 3
GND
Pin 4
Output 1 (switching output)
Pin 5
Multiplex input, connected to pin 4 of the master
sensor
6.3
Connection – synchronization mode
Sensors must be connected to the master sensor according to the following wiring
diagram:
4
2
5
Slave 1
4
2
5
Slave 2
4
2
5
Slave n
4
2
5 n.c.
Master
…
Out 1
Out 2
Out 1
Out 2
Out 1
Out 2
Out 2
Fig. 19: Wiring diagram – synchronization mode
The sensors do not have to be addressed. The master sensor controls all sensors in a fixed time
cycle with a trigger signal via pin 4:
RU40U…
RU130U…
RU300U…
RU600U…
22 ms
17.4 ms
37.4 ms
75.4 ms