Multiplex mode
Multiplex mode is used to prevent the mutual feedback of sensors operating at the same ultra-
sonic frequency. Up to ten devices can be operated in sequence. Each sensor operates at a
fixed time while all other sensors remain in wait mode. Multiplex mode must be set once for all
sensors via IO-Link. Each sensor is assigned a unique address between 1 and 10. The device
with the highest number set operates automatically as the master clock. This requires the
sensors to be interconnected.
NOTE
Multiplex mode is only possible with devices of the same type.
All connected sensors must have the same power and range in multiplex mode. In
multiplex mode, only connect sensors with the same ID no. The ID no. is marked on
each device.
Output 1 on the master device is not available in this mode. A teach-in operation is not possible
in this mode during operation. No other accessories are required for operation.
Synchronization mode
The mutual feedback of sensors operating at the same ultrasonic frequency can be prevented
in synchronization mode. Feedback is prevented since all sensors send and receive at the same
time. Any number of sensors can be operated in synchronization mode. The devices do not
have to be addressed. One of the sensors deployed is defined by the wiring as the master clock.
NOTE
Synchronization mode is only possible with devices of the same type.
All connected sensors must have the same power and range in synchronization
mode. In synchronization mode, only connect sensors with the same ID no. The ID
no. is marked on the device.
Output 1 on the master device is not available in this mode. A teach-in operation is not possible
in this mode during operation. No other accessories are required for operation.
Enable mode
Enable mode enables the targeted activation and deactivation of the sonic transducer of indi-
vidual sensors. In enable mode, each sensor is only active if a signal to U
B
is issued at pin 5. Syn-
chronization or multiplexing can be implemented in enable mode. Sensors with a different
power and range can be used at the same time in enable mode. An ultrasonic sensor is not
used as the master clock. The signal must be switched externally to each device via a PLC. The
sensors do not have to be interconnected. Inactive sensors output the valid values that were
last measured. The outputs can be used in the normal way. IO-Link operation is not possible in
this mode.